INSTALLATION DATA
ETC SINGLE STAGE ELECTRONIC
TEMPERATURE CONTROL
The Ranco® ETC is a microprocessor-based
family of electronic temperature controls,
designed to provide on/o control
for commercial heang, cooling, air
condioning and refrigeraon. The ETC
is equipped with a liquid crystal display
(LCD) that provides a constant read
out of the sensed temperature, and a
touch keypad that allows the user to
easily and accurately select the setpoint
temperature, dierenal and heang/
cooling mode of the operaon. Models
are available that operate on either line
voltage (120/208/240V AC) or low voltage
(24V AC).
APPLICATIONS
With its wide temperature setpoint range
and selectable heang or cooling modes,
the ETC can be used for a wide variety of
applicaons including refrigerated display
cases, walk-in and reach-in refrigerators,
milk coolers, refrigerated warehouses,
chillers, beer and beverage coolers,
tank heang, space and return air temperature
controls and condenser fan cycling.
FEATURES
• Wide setpoint temperature range (-30°F to 220°F) and dierenal
adjustment (1°F to 30°F)
• Simple keypad programming of setpoint temperature, dierenal
and cooling/heang modes
• LCD display readout of sensor temperature, control sengs,
relay status and onboard diagnoscs
• LED (Light Eming Diode) backlight to improve visibility of the display
in low light ambient applicaons.
• IP67 rated (water and dust resistant) thermistor-based probe to
remotely monitor temperature
• The sensor probe can be retroed in the eld by the use of factory
installed interconnect
• Remote temperature sensing up to 400 feet
• SPDT output relay
• User-selectable Fahrenheit/Celsius scales
• Lockout switch to prevent tampering by unauthorized personnel
• Choice of line voltage and low voltage models available
• Oponal 0 to 10 volt analog output available for remote temperature
indicaon
• An-short Cycle Compressor Delay for cooling applicaons
SPECIFICATIONS
Input Voltage 120 or 208/240V AC (24V AC oponal), 50/60 Hz
Temperature Range -30°F to 220°F
Dierenal Range 1°F to 30°F
Switch Acon SPDT
Sensor Thermistor, 1.94in. long x 0.25 in. diameter with
8 . cable, IP67 rated
Power Consumpon 120/208/240V AC: 100 Milliamps
24V AC: 2 - 6 VA
1
Relay Electrical Rangs 120V 208/240V
NO Contact
Full-load Amps 16 Amps 8 Amps
Locked rotor Amps 96 Amps 48 Amps
Resisve Amps 15 Amps 8 Amps
Horsepower 1 HP 1 HP
NC Contact
Full-load Amps 5.8 Amps 2.9 Amps
Locked rotor Amps 34.8 Amps 17.4 Amps
Resisve Amps 5.8 Amps 2.9 Amps
Horsepower 1/4 HP 1/4 HP
Pilot Duty: 125 VA at 120/208/240V AC
Control Ambient Temperature
Operang -20°F to 140°F (-29°C to 60°C)
Storage -40°F to 176°F (-40°C to 80°C)
Ambient Humidity 0 to 95%, RH, Non-condensing
0 to 10V Output Impedance 1K
Enclosure NEMA 1, Plasc
Agency Approvals UL Listed, File E94419, Guide XAPX
CSA Cered, File LR68340, Class 4813 02
ETC ORDERING INFORMATION
Uni-Line OEM Input No. of 0 - 10 V
Numbers Numbers Voltage Stages Output
ETC-111000-000 ETC-111020-000 120/240 1 No
ETC-111100-000 ETC-111120-000 120/240 1 Yes
ETC-112000-000 ETC-112020-000 24 1 No
ETC-112100-000 ETC-112120-000 24 1 Yes
OPERATION
Liquid Crystal Display (LCD)
The LCD display provides a constant read out of the sensor temperature
and indicates if the output relay is energized. When the S1 annunciator
is constantly illuminated during operaon, the relay is energized. The
display is also used with the keypad to allow the user to adjust the
setpoint temperature, dierenal and heang/cooling modes.
Backlight
When any of the 3 mode keys are pressed, the backlight is acvated
and the ETC is in control mode. Press the SET key to begin program
mode.
Control Setup
The temperature setpoint refers to the temperature at which the
normally open (NO) contacts of the output relay will open. Determine
the load (s) to be controlled and the operang mode required, cooling
or heang. Refer to Figure 1 for a visual representaon.
• When the cooling mode is chosen, the dierenal is above the
setpoint. The relay will de-energize as the temperature falls to the
setpoint.
• An-short Cycle Compressor Delay for cooling. Aer a relay
de-energizes, the ETC will prevent the relay from turning on unl a
congurable me has occurred to protect compressor.
• When the heang mode is chosen, the dierenal is below the
setpoint. The relay will de-energize as the temperature rises to the
setpoint.