Kaysun KRE Manuale utente

Categoria
Condizionatori d'aria a sistema split
Tipo
Manuale utente
KRE (Ventilazione a recupero di calore)
KRE-500D1
KRE-1000D1
KRE-1500D1
KRE-2000D1
Grazie mille per aver acquistato il nostro prodotto.
Prima di utilizzare l'unità, leggere attentamente questo manuale e conservarlo per
riferimento futuro.
MANUALE D'USO E INSTALLAZIONE
WARNING
If the supply cord is damaged, it must be replaced by the manufacturer or its service agent
or a similarly qualified person in order to avoid a hazard.
An all-pole disconnection device which has at least 3mm separation distance in all pole and
a residual current device(RCD)with the rating of above 10mA shall be incorporated in the
fixed wiring according to the national rule.
Disconnect the power supply before cleaning and maintenance.
The appliance shall be installed in accordance with national wiring regulations.
This appliance can be used by children aged from 8 years and above and persons with
reduced physical, sensory or mental capabilities or lack of experience and knowledge if they
have been given supervision or instruction concerning use of the appliance in a safe way
and understand the hazards involved.
Children shall not play with the appliance.
Cleaning and user maintenance shall not be made by children without supervision.
DISPOSAL: Do not dispose this product as unsorted municipal waste.
Collection of such waste separately for special treatment is necessary.
Directive 2002/96/EC (WEEE):
The symbol depicting a crossed-out waste bin that is underneath the appliance indicates
that this product, at the end of its useful life, must be handled separately from domestic
waste, must be taken to a recycling centre for electric and electronic devices or handed
back to the dealer when purchasing an equivalent appliance
AVVERTENZA
Se il cavo di alimentazione è danneggiato, deve essere sostituito dal costruttore o da un suo
rappresentante o da una persona qualificata per evitare rischi.
Un sezionatore onnipolare con una distanza tra i contatti di almeno 3 mm in tutti i poli e un
interruttore differenziale (RCD) con tensione nominale superiore a 10 mA devono essere
integrati nel cablaggio fisso in ottemperanza alle normative vigenti in materia di collegamenti
elettrici.
Prima della pulizia e della manutenzione, scollegare l’alimentazione.
L’apparecchiatura deve essere installata secondo le normative nazionali in materia di
cablaggio.
Questa apparecchiatura può essere utilizzata da bambini di età pari o superiore a 8 anni e da
persone con ridotte capacità fisiche, sensoriali o mentali o che non dispongono di esperienza
e conoscenze sufficienti, a condizione che vengano assistiti o istruiti in merito a un utilizzo
sicuro e ne abbiano compreso i pericoli relativi.
I bambini non devono giocare con l’apparecchiatura.
La pulizia e la manutenzione non devono essere effettuate da bambini senza supervisione.
SMALTIMENTO: Non smaltire il prodotto come rifiuto municipale indifferenziato.
Il prodotto necessita di una raccolta separata per un trattamento speciale.
Direttiva 2002/96/CE (RAEE):
Il simbolo del bidoncino sbarrato sotto l’apparecchiatura indica che questo prodotto, al
termine della sua vita utile, deve essere gestito separatamente dai rifiuti domestici e deve
essere portato presso un impianto di riciclaggio di apparecchiature elettriche ed elettroniche o
restituito al rivenditore all’acquisto di un’apparecchiatura equivalente
Ingresso aria esterna
Ventilatore
Ventilatore
Uscita aria di
espulsione
Filtro aria
Filtro aria
Nucleo scambiatore di calore
By-pass
Filtro aria
Uscita aria di mandata
Ingresso aria di ripresa
Ventilatore
Uscita aria di mandata
Filtro aria
By-pass
Ventilatore
Ingresso aria di ripresa
Nucleo scambiatore di calore
Condotto dell'aria in lamiera
Condotto dell'aria in lamiera
Ingresso aria esterna
Uscita aria di espulsione
PARTI PRINCIPALE DELL’UNITÀ
KRE 500D1 KRE 1000D1
KRE 1500D1 KRE 2000D1
1.
PRECAUTIONS
To prevent injury to the user or other people and property
damage, the following instructions must be followed. Incorrect
operation due to ignoring of instructions may cause harm or
damage. The appliance should be installed by a professional
in accordance with the specified instructions.
The safety precautions listed here are divided into two categories. In
either case, important safety informations are listed which must be
read carefully.
WARNING
Failure to observe a warning may cause electric shock,
fire hazard or personal injury
CAUTION
Failure to observe a caution may cause injury or damage
to the equipment.
WARNING
● Ask your dealer or qualified personnel to carry out
installation work. Do not try to install the machine by.
Incorrect installation may result in leakage, electric shocks
or fire.
● Installation should be done by following the installation
manual and no changes should be made to the unit.
Incorrect installation may cause leakage, electric shock, or
fire. If the KRE falls, it may cause damage and injury.
Install the unit on a foundation that is strong enough to
withstand the weight of the unit.
A foundation of insufficient strength may result in the
equipment falling and causing injuries.
Do not allow exhaust air to enter the outside air inlet.
This may cause the air of the room to become contaminated
, harming the health.
Locate the outside air intake vent so that it does not take in
exhaust air which contains combustion air, etc.
Incorrect installation may cause a loss of oxygen in the
room, leading to serious accidents.
Make sure that a separate power supply circuit is provided
for this unit and that all electrical work is carried out by
qualified personnel according to local laws and regulations
and this installation manual.
Insufficient power capacity, improper electrical works, or
incorrect wiring may cause electric shock or fire.
Make sure Earth Leakage Breaker is the type of all poles drop-out.
Be sure to ground.
Do not connect the ground wire to gas or water pipes, lightning rod
or a telephone ground wire.
Incomplete grounding may result in electric shocks.
● Make sure that all wiring is secured, the specified wires are used,
and no external forces act on the terminal connections or wires.
Improper connections or installation may result in overheating or
fore.
● When wiring the power supply and connecting the remote
controller wiring and transmission wiring, position the wires so that
the electric parts box lid can be securely fastened.
Improper positioning of the electric parts box lid may result in
electric shocks, fire or the terminals overheating.
CAUTION
Be sure to install an earth leakage breaker.
Failure to install an earth leakage breaker may result in
electric shocks.
● Install the indoor and outdoor units, power supply wiring and
connecting wires at least 1 meter away from television or
radio in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 meter may not
be sufficient enough to eliminate the noise.)
Install the two outdoor ducts with down slope to prevent
rainwater from entering the unit.
If this is not done completely, water may enter the building,
may damage furniture, etc.
Insulate the duct and the wall electrically when a metal duct is
to be penetrated through the metal lattice and wire lattice or
metal lining of a wooden structure wall.
Improper duct work may cause electric shocks or short
circuits.
● Make sure that a snow protection measure is taken. If no
protection snow may enter through the outdoor ducts, and
cause damaging furniture and electric shock and fire.
2. ACCESSORY
Table 2-1
Name Qty. Shape Purpose
Installation This must be delivered to the
and owner’s 1 manual customer
manual
NotesWired controller should be purchased separately.
Prepare the following on site.
Table 2-2
Name Purpose
For connecting unit’s drain pipe, which length
is selected according to your actual
PVC drain pipe requirement (Only required for Model 1500
and 2000
Damper For vibration damping, when lift the unit.
CONTENTS
PAGE
PRECAUTIONS. .......................................................... 1
ACCESSORY ............................................................. 1
INSTALLATION .......................................................... 2
WIRING .................................................................. 6
SPECIFICATION PARAMETER .......................................... 8
KRE APPLICATION. .................................................... 9
MAINTENANCE AND UPKEEP .......................................... 9
TRAIL RUN. ............................................................. 9
ERP INFORMATION. .................................................... 10
1.
PRECAUZIONI
Per evitare lesioni all'utente o ad altre persone e danni materiali,
è necessario seguire le seguenti istruzioni. Un funzionamento
errato dovuto all'inosservanza delle istruzioni può causare
lesioni o danni. L'apparecchio deve essere installato da un
professionista secondo le istruzioni specificate.
Le misure di sicurezza qui elencate sono suddivise in due categorie.
In entrambi i casi, sono elencate importanti informazioni di sicurezza
che devono essere lette attentamente.
AVVERTENZA
La mancata osservanza di un'avvertenza può causare
scossa elettrica, pericolo d'incendio o lesioni personali
ATTENZIONE
La mancata osservanza di un'avvertenza può causare
lesioni o danni all'apparecchiatura.
2. ACCESSORIO
AVVERTENZA
L’installazione deve essere effettuata dal rivenditore o da
personale qualificato. Non tentare di installare la macchina da
soli.
Un’installazione errata può causare perdite, scosse elettriche
o incendio.
L'installazione deve essere effettuata seguendo le istruzioni
riportate nell’apposito manuale e non devono essere
apportate modifiche all'unità.
Un’installazione errata può causare perdite, scosse elettriche
o incendio. Un’eventuale caduta dell’KRE può causare danni
o lesioni.
Installare l'unità su una base sufficientemente robusta da
resistere al peso dell'unità.
Una fondazione non sufficientemente resistente può causare
la caduta dell'attrezzatura e provocare lesioni.
Non far entrare l'aria espulsa nell'ingresso dell'aria esterna.
Questo può causare il contagio dell'aria del locale, con
conseguenti danni alla salute.
Posizionare la presa d'aria esterna in modo che non assorba
l'aria espulsa che contiene aria di combustione, ecc.
Un'installazione errata può causare una perdita di ossigeno
nel locale, con conseguenti gravi incidenti.
Accertarsi che questo apparecchio sia dotato di un circuito
di alimentazione separato e che tutti i lavori elettrici siano
eseguiti da personale qualificato in conformità alle leggi e ai
regolamenti locali e al presente manuale di installazione.
Un’alimentazione elettrica insufficiente o un cablaggio errato
possono causare scosse elettriche o incendi.
Tabella 2-1
Nome
Q.tà
Forma
Obiettivo
Manuale
d’uso e
d’installazione
1
Questo
manuale
deve essere consegnato
al cliente
Note: Il comando cablato deve essere acquistato separatamente.
Preparare sul posto quanto segue.
Tabella 2-2
Nome
Obiettivo
Tubo di
scarico in PVC
Per il collegamento del tubo di scarico
dell'unità, la cui lunghezza viene selezionata
in base alle reali esigenze (solo per i Modelli
1500D1 e 2000D1)
Smorzatore
Per lo smorzamento delle vibrazioni, quando
si solleva l'unità.
1
INDICE
PAGINA
PRECAUZIONI ............................................................................. 1
ACCESSORIO .............................................................................. 1
INSTALLAZIONE .......................................................................... 2
CABLAGGIO ................................................................................. 6
APPLICAZIONE KRE ................................................................... 9
PROVA IN BIANCO ...................................................................... 9
Assicurarsi che il sistema di protezione di dispersione a terra sia a
sezionamento di tutti i poli.
Assicurarsi di mettere a terra.
Non collegare il cavo di terra ai tubi del gas o dell'acqua, al
parafulmine o al cavo di terra del telefono.
Una messa a terra incompleta può causare scosse elettriche.
Assicuratevi che tutto il cablaggio sia fissato bene, che siano
utilizzati tutti i cavi specifici e che morsetti o cavi collegati non siano
sotto tensione.
Collegamenti o installazioni inadeguati possono provocare un
surriscaldamento o un surriscaldamento dell'apparecchio.
Durante il cablaggio dell'alimentatore e il collegamento del
cablaggio del comando remoto e della trasmissione, posizionare
i fili in modo che il coperchio del quadro elettrico possa essere
fissato saldamente.
Un errato posizionamento del coperchio del quadro elettrico può
causare scosse elettriche, incendi o surriscaldamento dei terminali.
ATTENZIONE
Accertarsi di installare un sistema di protezione di dispersione
a terra.
La mancata installazione di un interruttore di dispersione a terra
può causare scosse elettriche.
Installare le unità da interno ed esterno, il cablaggio
dell'alimentatore e i cavi di collegamento ad almeno 1 metro di
distanza dalla televisione o dalla radio per evitare interferenze o
disturbi dell'immagine.
(A seconda delle onde radio, una distanza di 1 metro può non
essere sufficiente.)
Installare i due condotti esterni con pendenza inferiore per
evitare che l'acqua piovana penetri nell'unità.
Se ciò non viene fatto completamente, l'acqua può entrare
nell'edificio, può danneggiare i mobili, ecc.
Isolare elettricamente il condotto e la parete quando un
condotto metallico deve essere penetrato attraverso il reticolo
metallico o il rivestimento metallico di una parete con struttura
in legno.
Un lavoro improprio dei condotti può causare scosse elettriche
o cortocircuiti.
Accertarsi che sia stata adottata una misura di protezione dalla
neve. In assenza di protezione la neve può penetrare attraverso
i condotti esterni, causando danni ai mobili, scosse elettriche e
incendi.
2
Fig. 3-1
Do not install the unit in the following locations:
Place subjected to high temperature or direct flame. May
result in fire or overheating.
Place such as machinery plant and chemical plate where
gas, which contains noxious gas or corrosive components
of materials such as acid, alkali organic solvent and plaint,
is generated. Place where combus tible gas leakage is
likely.
Copper piping and brazed joins may corrode, causing
refrigerant to leak or poisoning and fore due to leaked gas.
Place such as bathroom subjected to moisture.
Electric leak or electric shocks and other failure can be
caused.
Near machinery emitting electromagnetic waves.
Electromagnetic waves may disturb the operation of the
control system and result in a malfunction of the
equipment.
3.3 Preparations Before Installation
Confirm the positional relationship between the unit and
suspension bolts.
Leave space for servicing the unit and include
inspection hatches. (Always open a hole on the side of
the electric parts box so that the air filters, heat
exchange elements, fans, be easily be inspected and
serviced.)
Make sure the range of the unit’s external static
pressure is not exceeded.
Open the installation hole (Pre-setting ceilings)
Once the installation hole is opened in the ceiling where
the unit is to be installed, pass transmission wiring, and
remote controller wiring to the unit’s wiring holes.
After opening the ceiling hole, make sure ceiling is level
if needed. It might be necessary to reinforce the ceiling
frame to prevent shaking.
Please consult architect or woodworker, if necessary.
Install the suspension bolts. (Use M10 to M12
suspension bolts.) Use a hole-in anchor, sunken insert
anchor for existing ceilings, or other parts to be
procures in the field to reinforce the ceiling to bearing
the weight of the unit.
Install vibration damping feet. (For vibration damping)
3.
INSTALLATION
3.1 Installation Preparation
WARNING
Keep all the accessories and tools until installation work is
completed.
Leave the unit inside its packaging while moving, until
reaching the installation site. Where unpacking is
unavoidable, use a sling of soft material or protective
plates together with a rope when lifting, to avoid damage
or scratches to the unit.
Hold the unit by the hanger brackets when opening the
crate and moving it, and do not lift it holding on to any
other part (especially the duct connecting flange).
NOTE
Be sure to instruct customers how to properly operate the unit
(especially maintenance of air filter, and operation procedure)
by having them carry out operations themselves while looking
at the manual.
3.2 Select The Installation Site
CAUTION
When moving the unit during or after unpacking, make sure to
lift it by holding its hanger brackets. Do not exert any pressure
on other parts, especially duct connecting flange.
Select an installation site where the following conditions
are fulfilled and meet with your customer’s approval.
KRE should be installed far away from office, recreation
or any other places where silent environment are
required. (install that in special machine room or wash
room is recommended)
install in a place which has sufficient strength and
stability. (Beam, ceiling and other locations capable of
fully supporting the weight of the unit.) Insufficient
strength is dangerous. It may also cause vibration and
unusual operating noise.
Do not install the unit directly against a ceiling or wall. (If
the unit is in contact with the ceiling or wall, it can cause
vibration.)
Where sufficient clearance for maintenance and service
can be ensured.
CAUTION
Install the units, power supply wiring and connecting wires
at least 1 meter away from televisions or radios in order to
prevent interference or noise. (Depending on the
radio waves, a distance of 1 meter may not be sufficient
enough to eliminate the electric interference.)
The bellows may not be able to be used in some districts,
so exercise caution. contact your local government office
or fire department for details.
When discharging exhaust air to a common duct, the
Building Standard Law requires the use of fire proof
materials, so attach a 2m copper plate standing duct.
3.
INSTALLAZIONE
3.1 Preparazione all'installazione
AVVERTENZA
Conservare tutti gli accessori e gli utensili fino al termine dei
lavori di installazione.
Lasciare l'unità all'interno dell'imballo mentre ci si
sposta, fino a raggiungere il luogo di installazione. Se il
disimballaggio è inevitabile, utilizzare un'imbragatura di
materiale morbido o piastre di protezione insieme ad una
corda durante il sollevamento, per evitare danni o graffi
all'unità.
Afferrare l'unità con le staffe di aggancio quando si apre la
cassa e la si sposta, e non sollevare l'unità tenendola su
qualsiasi altra parte (in particolare la flangia di collegamento
del condotto).
NOTA
Assicurarsi di istruire i clienti su come utilizzare correttamente
l'unità (in particolare la manutenzione del filtro dell'aria e le
procedure operative) facendo in modo che essi stessi eseguano
le operazioni mentre guardano il manuale.
3.2 Selezionare il luogo di installazione
ATTENZIONE
Quando si sposta l'unità durante o dopo il disimballaggio,
assicurarsi di sollevarla tenendo le staffe di aggancio. Non
esercitare alcuna pressione su altre parti, in particolare sulla
flangia di collegamento del condotto.
Scegliere un luogo di installazione che soddisfi le condizioni
seguenti e sia approvato dal cliente.
L'KRE deve essere installato lontano da uffici, attività
ricreative o qualsiasi altro luogo in cui è richiesto un
ambiente silenzioso (si consiglia di installarlo in un locale
macchine speciale o in un bagno)
Installare in un luogo che abbia sufficiente resistenza
e stabilità. (Trave, soffitto e altre posizioni in grado di
sostenere completamente il peso dell'unità.) Un supporto
non sufficientemente resistente è pericoloso, poiché
può anche causare vibrazioni e rumori di funzionamento
insoliti.
Non installare l'apparecchio direttamente contro il soffitto o
la parete. (Se l'apparecchio è a contatto con il soffitto o la
parete, può causare vibrazioni.)
Dove è possibile garantire uno spazio sufficiente per la
manutenzione e l'assistenza.
ATTENZIONE
Installare le unità, il cablaggio dell'alimentatore e i cavi di
collegamento ad almeno 1 metro di distanza da televisori
o radio per evitare interferenze o disturbi. (A seconda delle
onde radio, una distanza di 1 metro potrebbe non essere
sufficiente ad eliminare l'interferenza elettrica.)
Il soffietto potrebbe non poter essere utilizzato in alcuni
distretti, quindi fate attenzione. Contattate l'ufficio governativo
locale o i vigili del fuoco per i dettagli.
Quando si scarica l'aria espulsa in un condotto comune, la
legge standard dell'edilizia richiede l'uso di materiali ignifughi,
quindi collegare un condotto stazionario di 2 m in rame.
Non installare l'unità nei luoghi seguenti:
Luogo sottoposto ad alta temperatura o a fiamma diretta.
Può provocare incendi o surriscaldamento.
Luogo come l'impianto di macchinari e piastra chimica
dove si genera gas, che contiene gas nocivi o
componenti corrosivi di materiali come acidi, solventi
organici alcalini e vernici. Luogo in cui è probabile che
si verifichino fughe di gas commestibile da pettine.
Le tubazioni in rame e le giunzioni brasate possono
corrodersi, causando perdite di refrigerante o
avvelenamento e la fuoriuscita di gas.
Luogo come il bagno sottoposto ad umidità.
Possono verificarsi perdite elettriche o scosse elettriche
e altri guasti.
Vicino a macchinari che emettono onde elettromagnetiche.
Le onde elettromagnetiche possono disturbare il
funzionamento del sistema di controllo e causare un
malfunzionamento dell'apparecchio.
3.3 Preparazione prima dell'installazione
Confermare il rapporto di posizione tra l'unità e i bulloni di
sospensione.
Lasciare spazio per la manutenzione dell'unità e includere
boccaporti di ispezione. (Aprire sempre un foro sul
lato del quadro elettrico in modo che i filtri dell'aria, gli
elementi di scambio termico, i ventilatori, siano facilmente
ispezionabili e di facile manutenzione)
Accertarsi che il campo della pressione statica esterna
dell'unità non venga superato.
Aprire il foro di installazione (Pre-regolazione dei soffitti)
Una volta aperto il foro di installazione nel soffitto dove
deve essere installata l'unità, passare il cablaggio della
trasmissione e il cablaggio del comando remoto attraverso
i fori di cablaggio dell'unità.
Dopo aver aperto il foro nel soffitto, assicurarsi che il soffitto
sia in piano, se necessario. Potrebbe essere necessario
rinforzare il telaio del soffitto per evitare scosse.
Consultare l'architetto o il falegname, se necessario.
Installare i bulloni di sospensione. (Utilizzare bulloni di
sospensione da M10 a M12.) Utilizzare un ancoraggio
forato, un ancoraggio con inserto incassato per soffitti
esistenti, o altre parti da procurarsi sul campo per
rinforzare il soffitto fino a sostenere il peso dell'unità.
Installare i piedini antivibranti. (Per lo smorzamento delle
vibrazioni)
Struttura in legno
Far passare i bastoni rettangolari attraverso le travi, e posizionare
i bulloni a sospensione.
Campata in legno
Trave
Soffitto
Bullone a sospensione (da M10 a M12)
Vecchio calcestruzzo grezzo
Utilizzare bulloni e tappi incorporati.
Fig. 3-1
3
Outdoor air TEMP. -7 ~43
TION Room TEMP. 0 ~43
OPERA
Lower than 80%
If higher than 80%, the surface of
Room humidity indoor unit may be condensed or
the condensate will be blown from
air outlet.
multiple indoor units (see Figure 7.8);
Unitmm
Protection or error may occur if running the unit beyond the above
condition, and will cause unit stop running.
Fig. 3-2
3.4 Installation
Before installation, please confirm all external parts are
stand in their place and without damage.
The surrounding environment of the unit, especially the
sides of wiring cabinet and water collecting side should
reserve sufficient wiring and maintenance and space;
additionally, one should ensure the removing space for
filter griller.
Unit should mount steadily and without sustain the weight
form condensate water pipe and air duct. The vents of air
inlet/outlet and return should be connected with flexible
tube.
Unit in AC 220-240V/50Hz, reliable grounding; each one
possesses of independent cut-off and protection device.
The installation dimension and maintenance space. (See
the following attached picture Fig.3-3 )
Operating conditions
For proper performance, run the air conditioner under the
following temperature conditions:
Unità: mm
Struttura trave e trave in acciaio
Posizionare e utilizzare un angolo di supporto in acciaio.
Nuovo calcestruzzo grezzo
Posizionarlo utilizzando le boccole o i bulloni incorporati.
Fig. 3-2
più unità da interno (vedere Figura 7.8);
3.4 Installazione
Prima dell'installazione, verificare che tutte le parti
esterne siano al loro posto e senza danni.
L'ambiente circostante dell'unità, in particolare i lati
dell'armadio elettrico e il lato di raccolta dell'acqua,
dovrebbe riservare spazio sufficiente per cablaggio e
manutenzione; inoltre, si dovrebbe garantire lo spazio
necessario per la rimozione della griglia del filtro.
L'unità deve essere montata costantemente e senza
sostenere il peso del tubo dell'acqua di condensa e
del condotto dell'aria. Le bocchette di ingresso/uscita
dell'aria e di ritorno devono essere collegate con un tubo
flessibile.
Unità in AC 220-240 V/50 Hz, messa a terra affidabile;
ognuna di esse è dotata di dispositivo indipendente di
spegnimento e protezione.
La dimensione di installazione e lo spazio di
manutenzione. (Vedere la seguente figura allegata
Fig.3-3)
Condizioni operative
Per un corretto funzionamento, far funzionare il
condizionatore d'aria nelle seguenti condizioni di temperatura:
FUNZIONAMENTO
Aria esterna TEMP.
-7
~43
TEMP. ambiente
0 ~43
Umidità ambiente
Inferiore a 80%
Se superiore all'80%, la superficie
dell'unità da interno può essere
condensata o la condensa viene
soffiata dall'uscita dell'aria.
Se l'unità funziona in condizioni diverse da quelle sopra indicate,
può verificarsi una protezione o un errore che può causare
l'arresto dell'unità.
Bullone sospeso
Bullone a
sospensione
Angolo di supporto
in acciaio
Inserto a
linguetta
Inserto
scorrevole
Calcestruzzo
ferroso
Bullone integrato
(Con bullone
integrato nel tubo)
H
450
4 05
1000
400
L
W
Spazio per la manutenzione
4
Model L L1 L2 W1 W2 W H H1 N N1
KRE 500
1071 1138 1311 1005 465 1106 390 227 Φ244 195
KRE 1000
1071 1138 1311 1431 764 1526 390 230 Φ244 195
Table 3-1 (Unit:mm)
Tabella 3-1 (Unità: mm)
Dimensioni chiave dell'unità e dell'installazione del condotto dell'aria. (Vedere le seguenti figure Fig.3-4~3-6 e Tabella 3-1)
KRE 500D1~KRE 1000D1
H
N1
Uscita aria di espulsione Ingresso aria di ripresa
W1
Ingresso aria esterna Uscita aria di mandata
Fig. 3-4
Modello
L
L1
L2
W1
W2
W
H
H1
N
N1
KRE 500D1
1071
1138
1311
1005
465
1106
390
227
Φ244
195
KRE 1000D1
1071
1138
1311
1431
764
1526
390
230
Φ244
195
H1
Sistema
by-pass
W2
L
L1
L2
W
N
5
120
320
346
370
1300
1270
350
KRE 1500D1
Sistema by-pass
Dimensione della flangia
Ingresso aria di ripresa Uscita aria di
espulsione
Uscita aria di mandata Ingresso
aria esterna
1690
1740
Fig. 3-5
KRE 2000
Dimensione della flangia
Ingresso aria di ripresa Uscita aria di
espulsione
Uscita aria di mandata
1761
1811
Ingresso aria esterna 120
320
346
370
Fig. 3-6
320
320
650
1425
Centralina
elettrica
320
320
750
1625
Centralina
elettrica
1500
1470
252
252
685
60
615
60
350
326
326
300
300
300
300
300
300
6
KRE 200~ KRE 2000D1
Phase Single phase
Power supply Voltage 220-240V/50Hz
/frequency
Input current
see 10. Electrical
Main switch Characteristics table
/fuse(A)
3 (Earthing line
Wire’s qty should be used
Power supply
yellow/green wire.)
wireDimension Wire
cross
-section 2.5
(mm2)
ENC1 Capacity setting
0200
1300
2 400
3 500
4 800
5 1000
6 1500
7 2000
ON
ON Low static pressure
1 2
SW1-1
ON
OFF High static pressure
1 2
ON
ON KRE centralized control
1 2
SW1-2 ON
OFF KRE single unit operation
1 2
ON
ON With PRO (reserved)
1 2 3
SW2-1 ON
OFF
Without PRO (reserved)
1 2 3
ON
ON Positive Pressure
1 2 3
SW2-2
ON
OFF Negative Pressure
1 2 3
ON
ON
SW2-2
1 2 3
SW2-3
ON
OFF
Balance Pressure
1 2 3
Table 4-1
After wiring, please confirm all connections are correct,
and then power to the unit.
Pay attention to the power supply wire of three-phase
model; confirm the phase sequence of which is correct.
4.1 Electric data Specification
4.
WIRING
Warning
All the supplied parts, materials and electrical works must
comply with local regulations.
Only use copper wires.
Use a steady power supply for the air-conditioners. The
power voltage must be in line with the rated voltage.
The electrical wiring works must be carried out by a
professional technician, and must comply with the labels stated
in the circuit diagram.
Before the electrical connection works are carried out, turn
off the power supply to prevent injuries caused by electric
shock.
The external power supply circuit of the air conditioner must
include an earth line, and the earth line of the power cord
connecting to the indoor unit must be securely connected to
the earth line of the external power supply.
Leakage protective devices must be configured according to the
local technical standards and requirements for electrical and
electronic devices.
The fixed wiring connected must be equipped with an all-pole
disconnection device with a minimum 3 mm contact
separation.
The distance between the power cord and signal line must be
at least 300 mm to prevent the occurrences of electrical
interference, malfunction or damage to electrical
components. At the same time, these line must not be in
contact with the piping and valves.
Choose electrical wiring that conforms to the corresponding
electrical requirements.
Connect to the power supply only after all the wiring and
connections have been completed, and check carefully if the
connection is correct.
figure of the power supply terminal
POWER INPUT
Fig. 4-1
When connecting to the power supply terminal, use the circular wiring
terminal with insulation.
Use power cord that conforms to the specifications and connect the
power cord firmly. To prevent the cord from being pulled out by
external force, make sure it is fixed securely.
If circular wiring terminal with insulation cannot be used, please make
sure that:
Do not connect two power cords with different diameters to the
same power supply terminal (may cause overheating).
Table 4-2
ENC1 Settings for Capacity SW1 Setting for static pressure
INGRESSO ALIMENTAZIONE
Fig. 4-1
Nel collegamento al morsetto dell’alimentazione elettrica, utilizzare il
morsetto del cablaggio circolare con involucro isolante.
Utilizzare un cavo di alimentazione conforme alle specifiche e collegarlo
saldamente. Per impedire al cavo di essere tirato dall’esterno,
assicurarsi che sia fissato saldamente.
Se il morsetto del cablaggio circolare con involucro isolante non p
essere usato, assicurarsi di:
Non collegare allo stesso morsetto due cavi di alimentazione con
diametri diversi (questo può causare un surriscaldamento).
4.
CABLAGGIO
Avvertenza
Le parti, i materiali e i lavori elettrici devono essere conformi alle
norme vigenti.
Utilizzare esclusivamente cavi in rame.
I condizionatori d'aria devono utilizzare una presa di alimentazione
dedicata. La tensione di alimentazione deve essere in linea con la
tensione nominale.
I lavori di cablaggio elettrico devono essere effettuati da un tecnico
qualificato e devono essere conformi alle etichette dello schema
circuitale.
Prima di eseguire lavori di collegamento elettrico, scollegare
l’alimentazione per impedire che scosse elettriche possano
causare lesioni.
Il circuito di alimentazione esterno del condizionatore deve
includere una linea di terra, e la linea di terra del cavo di
alimentazione all’unità da interno deve essere collegata in modo
sicuro alla linea di terra dell’alimentazione esterna.
I dispositivi di protezione contro le perdite devono essere
configurati in conformità alle norme tecniche vigenti e ai requisiti
per i dispositivi elettrici ed elettronici.
Il cablaggio fisso collegato deve essere dotato di un sezionatore
onnipolare con una distanza tra i contatti di almeno 3 mm in tutti
i poli.
Il cavo di alimentazione deve rispettare una distanza di almeno
300 mm dalla linea di segnalazione per evitare interferenze
elettriche, malfunzionamenti o danni ai componenti elettrici. Allo
stesso modo, queste linee non devono entrare in contatto con le
tubazioni e le valvole.
Il cablaggio elettrico deve essere conforme ai requisiti elettrici
corrispondenti.
Una volta concluse le operazioni di cablaggio e collegamento
e dopo aver verificato la correttezza, collegare l’alimentazione
elettrica.
4.1 Specifiche dei dati elettrici
Tabella 4-1
KRE 200D1~ KRE 2000D1
Alimentazione
Fase
Monofase
Tensione
/frequenza
220-240 V/50 Hz
Corrente di ingresso Interruttore
principale
/fusibile (A)
vedere 10. Tabella
delle Caratteristiche
elettriche
Cavo di
alimentazione
Dimensioni
Q.tà del filo
3 (Per la linea di
messa a terra usare
filo giallo/verde.)
Sezione trasversale
del cavo
(mm2)
2,5
Dopo il cablaggio, verificare che tutti i collegamenti siano
corretti e quindi alimentare l'unità.
Prestare attenzione al cavo di alimentazione del modello
trifase; verificare la corretta sequenza delle fasi.
Tabella 4-2
ENC1 Impostazioni per la potenza SW1 Impostazione per la pressione
statica
figura del morsetto di alimentazione
Fig. 4-2 Fig. 4-3
ENC1
Impostazione di potenza
0
200
1
300
2
400
3
500
4
800
5
1000
6
1500
7
2000
SW1-1
ON
Bassa pressione statica
OFF
Alta pressione statica
SW1-2
ON
Comando centralizzato KRE
OFF
Funzionamento unità singola
KRE
SW2-1
ON
Con PRO (riservato)
OFF
Senza PRO (riservato)
SW2-2
ON
Pressione positiva
OFF
Pressione negativa
SW2-3
ON
SW2-2
OFF
Pressione di equilibrio
+
Morsetto del cablaggio
circolare
Filo di rame
Tubo isolante
Corretti collegamenti per il cablaggio dell'alimentazione
Cavo di
alimentazione
L
N
7
Operation Flashing Show on Explanation
lamp times centralized controller
● / / Unit is ON
○ / / Unit is OFF
Indoor temperature
E2 sensor error
4E5(new protocol) Outdoor temperature
EF(old protocol) sensor error
6E7 EEPROM error
8E6 DC fan motor error
10 OFF LINE Without address
Communication error
12 E1 with ODU
14 Ip address Conflict
16 EU error with sensor board
18 FC
error with CO2 sensor
wire controller
E9 communication failure
Ed Outdoor unit failure
CODE CN8 CN9 CN32 CN33 CN7 CN3 CN4
CN21
NAME
P Q E
X Y E
U*
D1D2E X1X2
In
doo
rt
emp
. S
ensor O
u
t
do
o
rte
m
p. Se
nsor
CN31 reserved
CN16 Force to exhaust air mode
CN26
Remote ON/OFF
CN14
Si an
CN15 Alarm
CN20
Signal for inlet air Pre-heat
Communication wiring between the indoor and outdoor units
The KRE and outdoor units communicate via the RS485 serial port.
The communication wiring between the KRE and outdoor units should be connected one unit after
another in a daisy chain from the outdoor unit to the final KRE unit. And the shielded layer must be
properly grounded, and a build-out resistor must be added to the last KRE unit to enhance the stability
of the communication system.
Incorrect wiring such as a star connection or a closed ring will cause instability of the communication
system and system control anomalies.
Use a three core shielded wire (greater than or equal to 0.75 mm2) for the communication wiring
between the indoor and outdoor units. Make sure the wiring is connected correctly. The connecting lead
for this communication wire must come from the master outdoor unit.
All shielded wiring in the network are interconnected, and will eventually connect to earth at the same
point " .
*reserved
Table 4-4 Terminal Definition
Table 4-3 Code and Definitions
NOTE: :Light ; :Extinguish ; :Quick flash
Tabella 4-3 Codici e definizioni
NOTA: :Accesa;
:Spenta;
:Lampeggio rapido
Spia
funzionamento
Num.
lampeggi
Indicato sul comando
centralizzato
Spiegazione
/
/
L’unità è accesa (ON)
/
/
L’unità è spenta (OFF)
E2
Errore del sensore di temperatura
interna
4
E5(nuovo protocollo)
EF(vecchio protocollo)
Errore del sensore di
temperatura esterna
6
E7
Errore EEPROM
8
E6
Errore motore ventilatore DC
10
OFFLINE
Senza indirizzo
12
E1
Errore di comunicazione
con ODU
14
Conflitto indirizzo Ip
16
EU
errore scheda sensore
18
FC
errore sensore di rilevamento
CO2
E9
errore di comunicazione
comando cablato
Ed
Errore unità da esterno
Tabella 4-4 Definizione morsetti
CODICE
CN8
CN9
CN32
CN33
CN7
CN3
CN4
CN21
NOME
P Q E
X Y E
-
D1D2E
X1X2
Sensore di temp. interna
Sensore di temp. esterna
-
*riservato
Unità da
esterno (Collegare l’estremità schermata del cavo schermato alla
lamiera della centralina elettronicaqui)
(
(P
P
Q
Q
E
E)
)
Linea di segnale
tra le unità da esterno
Collegare lo strato schermato del cavo schermato
(
(P
P
Q
Q
E
E)
)
Unità da interno ed
esterno
Cavo di comunicazione
Solo l’ultima unità da interno richiede l’aggiunta
P di un resistore esterno su P e Q.
Q
(aprire)
Cablaggio di comunicazione tra unità da interno ed esterno
Le unità da esterno e KRE comunicano mediante la porta seriale RS485.
Il cablaggio di comunicazione tra le unità da esterno e KRE deve essere collegato a margherita un’unità
dopo l’altra, da quella da esterno fino all’KRE finale. Lo strato schermato deve essere correttamente
messo a terra, con l’aggiunta di un resistore esterno all’ultima unità KRE per accrescere la stabilità del
sistema di comunicazione.
Non utilizzare collegamenti a stella o anello chiuso perché scorretti: sono causa di instabilità al sistema di
comunicazione e anomalie al sistema di regolazione.
Utilizzare un cavo schermato a tre fili (pari o maggiore a 0,75 mm2) per il cablaggio di comunicazione tra
questo cavo di comunicazione deve provenire dall’unità da esterno master.
L’intero cablaggio schermato nella rete è interconnesso, e infine collegato a terra nello stesso punto " ”.
Resistore
esterno
Contatto
pulito
(entrata)
CN31
riservato
CN16
Forza modali aria di espulsione
CN26
ON/OFF remoto
Contatto
pulito
(uscita)
CN14
Riservato
CN15
Allarme
CN20
Segnale per preriscaldamento
aria in ingresso
8
Opera o Manual
There are two types of precautions as described below:
Warning: Failure to comply may lead to death or serious injury.
Caution: Failure to comply may lead to injury or damage of the
unit. Depending on the situation, this may also lead to serious injury.
Once the installation is completed, please keep the manual properly
for future reference. When this air conditioner is handed over to other
users, make sure that the manual is included with the handover.
Warning
Do not use this unit in locations where flammable gas may exist. If
flammable gas comes into contact with the unit, a fire may occur,
which could result in serious injury or death.
If this unit exhibits any abnormal behavior (such as emitting
smoke) there is adanger of serious injury. Disconnect the power
supply and contact your supplier or service engineer immediately.
The refrigerant in this unit is safe and should not leak if the system
is designed and installed properly. However, if a large amount of
refrigerant leaks into a room, the oxygen concentration will
decrease rapidly, which can cause serious injury or death. The
refrigerant used in this unit is heavier than air, so the danger is
greater in basements or other underground spaces. In the event of
a refrigerant leak, turn off any devices that produce a naked flame
and any heating devices, ventilate the room, and contact your
supplier or service engineer immediately.
Toxic fumes may be produced if the refrigerant in this unit comes
into contact with naked flames (such as from a heater, gas
stove/burners, or electric appliances).
Fig. 4-5
Communication wiring between the indoor unit and wired controller
The wired controller and the indoor unit can be connected in different manners, depending on the forms of
communication.
1.
For a bidirectional communication mode:
Use 1 wired controller to control 1 indoor unit or 2 wired controllers (one master and one slave
controller) to control 1 indoor unit.(see Fig.4-4)
Use 1 wired controller to control multiple indoor units or 2 wired controllers (one master and one slave
controller) to control multiple indoor units. The maximum number of connections is 16.(see Fig.4-5)
2.
For single direction communication mode:
Use 1 wired controller to control 1 indoor unit
The X1/X2, D1/D2 ports on the sides of the main control board and single direction communication port
are for different types of wired controllers.
For the specific connection method, refer to the instructions in the corresponding wired controller
manual to carry out the wiring and connections.
Handling the Electrical Wiring Connection Points
Once the wiring and connections are done, use tie straps to secure the wiring properly so that the
connection joint cannot be pulled apart by external force. The connection wiring must be straight out so
that the cover of the electrical box is level and can be closed tightly.
Cablaggio di comunicazione tra l’unità da interno e il comando cablato
Il comando cablato e l’unità da interno possono essere collegati in diversi modi, a seconda delle forme di
comunicazione.
1. Per una modalità di comunicazione bidirezionale:
Utilizzare 1 comando cablato o 2 comandi cablati (uno master e uno slave) per controllare 1 unità da interno
(vedere Figura 4-4)
Utilizzare 1 comando cablato o 2 comandi cablati (uno master e uno slave) per controllare diverse unità da
interno. Il numero massimo di collegamenti è 16 (vedere Fig.4-5).
2. Per una modalità di comunicazione unidirezionale:
Utilizzare 1 comando cablato per controllare 1 unità da interno
Le porte X1/X2, D1/D2 ai lati della scheda di controllo principale e la porta di comunicazione unidirezionale
sono per diversi tipi di comandi cablati.
Per il collegamento, fare riferimento alle istruzioni del manuale del comando cablato, relative a cablaggio e
collegamenti.
3. i gruppi devono essere composti solo da unità KRE-2B. Non sono ammessi gruppi composti da unità miste di
diverso tipo (es. 2nd gen. IDUs+KRE-2B).
Trattamento dei punti di collegamento del cablaggio elettrico
Una volta posato il cablaggio ed eseguiti i collegamenti, fissare e assicurare il cablaggio in modo adeguato,
così da impedire che una forza esterna possa esercitare una trazione sul punto di collegamento. Tenere diritto
il collegamento del cablaggio in modo che non vi siano dislivelli che impediscano di chiudere perfettamente il
coperchio del quadro elettrico.
Usare materiali isolanti e sigillanti di tipo professionale, per sigillare e proteggere cavi forati. Una
sigillaturainadeguata può portare a condensazione e favorire l’ingresso di piccoli animali o insetti che
possono causare cortocircuiti in parti dell’impianto elettrico, provocandone il guasto.
Fig. 4-4
Il refrigerante in questa unità è sicuro e non dovrebbe perdere, se
l’impianto è concepito e installato correttamente. Tuttavia, in caso
di fuoriuscita di una grande quantità di refrigerante in un ambiente,
la concentrazione di ossigeno diminuirà rapidamente, arrivando a
causare lesioni gravi. Il refrigerante usato in questa unità è più
pesante dell’aria, pertanto il pericolo è maggiore in seminterrati o
altri spazi sotterranei. In caso di perdita di refrigerante, spegnere
tutti i dispositivi che producono fiamme libere e qualsiasi dispositivo
di riscaldamento, arieggiare l’ambiente e contattare il rivenditore o
tecnico dell’assistenza immediatamente.
Se il refrigerante di questa unità entra in contatto con fiamme
libere (come quella di una resistenza, bruciatori/fornelli a gas o
apparecchiature elettriche), è possibile che si producano fumi tossici.
Fig. 4-5
Comando cablato master
Comando cablato slave
Manuale operativo
Qui di seguito sono descritti due tipi di precauzioni:
Avvertenza: La mancata osservanza di questo tipo di indicazione può
causare lesioni gravi.
Attenzione: La mancata osservanza di questo tipo di indicazione
può portare a lesioni alla persona o a danni all’unità. A seconda delle
circostanze, può anche causare gravi lesioni.
Una volta completata l’installazione, conservare il manuale in maniera
adeguata per futuro riferimento. Qualora questo condizionatore sia
acquisito da altri utenti, assicurarsi di trasmettere contestualmente anche
questo manuale.
Avvertenza
Non utilizzare questa unità in luoghi dove possono essere presenti
gas infiammabili. Qualora l’unità venisse a contatto con gas
infiammabile, ciò potrebbe causare un incendio, con conseguenti
lesioni gravi.
In caso di comportamento anomalo della presente unità (ad
esempio se emettesse fumo), si rischiano lesioni gravi. Scollegare
l’alimentazione e contattare immediatamente il rivenditore o un
tecnico dell’assistenza.
P
Q
E
X
TX RX E
D1
D2
E
X1
X2
X1
X2
X1
X2
X2 X1 D2 D1
X2 X1 D2 D1
X1 X2 X1 X2 X1 X2
PQ E XEY TXRXED1 D2 ED1
PQ E XEY D2 E
T
XRXEPQ E XEY T
XRXED1D2 E
Comando cablato 1 Comando cablato 2
Comando cablato master Comando cablato slave
Unità da interno 1 Unità da interno 2 Unità da interno n (n<=16)
9
CAUTION
1. Never turn screws too tightly, or else the cover would be dented or the Liquid Crystal breaks.
2. Please leave sufficient space for maintenance and service of wired controller.
3. Wired controller should be purchased separately.
4. Please follow the installation and owner’s manual of wired controller.
If this unit is used in the same room as a cooker, stove, hob, or
burner, ventilation for sufficient fresh air must be ensured,
otherwise the oxygen concentration will fall, which may cause
injury.
Dispose of this unit’s packaging carefully, so children cann’t play
with it. Packaging, especially plastic packaging, can be
dangerous, can cause serious injury or death. Screws, staples
and other metal packaging components can be sharp and should
be disposed of carefully to avoid injury.
Dispose of this unit’s packaging carefully, so children cann’t play
with it. Packaging, especially plastic packaging, can be
dangerous, can cause serious injury or death. Screws, staples
and other metal packaging components can be sharp and should
be disposed of carefully to avoid injury.
Do not attempt to inspect or repair this unit yourself. This unit
should only be serviced and maintained by a professional air
conditioning service engineer. Incorrect servicing or maintenance
can cause electric shocks, fire or water leaks.
This unit should only be re-positioned or re-installed by a
professional technician. Incorrect installation can lead to electric
shocks, fire or water leaks. The installation and grounding of
electrical appliances should only be carried out by licensed
professionals. Ask your supplier or installation engineer for further
information.
Do not allow this unit or its remote controller to come into contact
with water, as this can lead to electric shocks or fire.
Turn off the unit before cleaning it to avoid electric shocks.
Otherwise, an electric shock and injury may result.
To avoid electric shocks and fires, install an earth leakage
detector.
Do not use paint, varnish, hair spray, other flammable sprays or
other liquids that may give off flammable fumes/vapor near this
unit, as doing so can cause fires.
When replacing a fuse, ensure that the new fuse to be installed
completely complies with requirements.
Do not open or remove the unit's panel when the unit is powered
on. Touching the unit's internal components while the unit is
powered on can lead to electric shocks or injuries caused by
moving parts such as the unit's fan.
Ensure that the power supply is disconnected before any servicing
or maintenance is carried out.
Do not touch the unit or its remote controller with wet hands, as
doing so can lead to electric shocks.
Do not allow children to play near this unit, as doing so risks injury
Do not insert your fingers or other objects into the unit’s air inlet or
air outlet to avoid injury or damage to the equipment.
Do not spray any liquids onto the unit or allow any liquids to drip
onto the unit.
Do not place vases or other liquid containers on the unit or in
places where liquid could drip onto it. Water or other liquids that
come into contact with the unit can lead to electric shocks or fires.
Do not remove the remote controller’s front or back overs and do
not touch the remote controller’s internal components, as doing so
can cause injury. If the remote controller stops working, contact
your supplier or service engineer.
Ensure that the unit is properly grounded, otherwise electric
shocks or a fire may result. Electrical surges (such as those that
can be caused by lightning) can damage electrical equipment.
Ensure that suitable surge protectors and circuit breakers are
properly installed, otherwise electric shocks or a fire may result.
Dispose of this unit properly and in accordance with regulations. If
electrical appliances are disposed of in landfills or dumps,
hazardous substances can leak into the groundwater and thus
enter the food chain.
Do not use the unit until the qualified technician instructs you that
it is safe to do so.
Do not place appliances that produce naked flames in the path of
the airflow from the unit. The airflow from the unit may increase the
rate of combustion, which may cause a fire and cause serious
injury or death. Alternatively, the airflow may cause incomplete
combustion which can lead to reduced oxygen concentration in
the room, which can cause serious injury or death.
Caution
Only use the air conditioner for its intended purpose. This unit
should not be used to provide refrigeration or cooling for food,
plants, animals, machinery, equipment or art.
Do not insert your fingers or other objects into the unit’s air inlet or
air outlet to avoid injury or damage to the equipment.
The fins on the unit’s heat exchanger are sharp and can cause
injury if touched. To prevent injury, when the unit is being serviced,
gloves should be worn or the heat exchanger should be covered.
Do not place items which might be damaged by moisture under
the unit. When the humidity is greater than 80% or if the drain pipe
is blocked or the air filter is dirty, water could drip from the unit and
damage objects placed under the unit.
Ensure that the drain pipe functions properly. If the drain pipe is
blocked by dirt or dust, water leaks may occur when the unit is
running in cooling mode. If this happens, turn the unit off and
contact your supplier or service engineer.
Do not touch the internal parts of the controller. Do not remove the
front panel. Some internal parts may cause injury or be damaged.
Ensure that children, plants and animals are not directly exposed
to the airflow from the unit.
When fumigating a room with insecticide or other chemicals, cover
the unit well and do not run it. Failure to observe this caution could
lead to chemicals getting deposited inside the unit and later
emitted from the unit when it running, endangering the health of
any room occupants.
Do not dispose of this product as unsorted waste. It must be
separately collected and processed. Ensure that all applicable
legislation regarding the disposal of refrigerant, oil and other
materials is adhered to. Contact your local waste disposal authorty
for information about disposal procedures.
To avoid damaging the remote controller, exercise caution when
using it and replacing its batteries. Do not place objects on top of it.
Do not place appliances that have naked flames under or near
the unit, as heat from the appliance can damage the unit.
Do not place the unit’s remote controller in direct sunlight. Direct
sunlight can damage the remote controller’s display.
Do not use strong chemical cleaners to clean the unit, as doing so
can damage the unit’s display or other surfaces. If the unit is dirty
or dusty, use a slightly damp cloth with very diluted and mild
detergent to wipe the unit. Then, dry it with a dry cloth.
Children shall not play with the appliance.
ATTENZIONE
Se questa unità viene utilizzata nello stesso ambiente dove è
presente un fornello, cucina, piastra o bruciatore, assicurare
una ventilazione sufficiente per l’aria esterna, per impedire una
diminuzione della concentrazione di ossigeno pericolosa per la
salute.
Smaltire l’imballaggio di questa unità con attenzione e fuori
dalla portata dei bambini. Gli imballaggi, in particolare quelli
in plastica, possono essere pericolosi e causare lesioni
gravi. Le viti, le graffette e altri componenti metallici
dell’imballaggio possono essere appuntiti e dovrebbero essere
smaltiti con cautela per impedire lesioni.
Smaltire l’imballaggio di questa unità con attenzione e fuori
dalla portata dei bambini. Gli imballaggi, in particolare quelli
in plastica, possono essere pericolosi e causare lesioni
gravi. Le viti, le graffette e altri componenti metallici
dell’imballaggio possono essere appuntiti e dovrebbero essere
smaltiti con cautela per impedire lesioni.
Non tentare di ispezionare o riparare l’unità da soli. Gli
interventi di riparazione e manutenzione sull’unità devono
essere effettuati esclusivamente da un tecnico dell’assistenza
qualificato. Interventi di riparazione o manutenzione non corretti
possono causare scosse elettriche, fiamme o perdite d’acqua.
L’unità dovrebbe essere riposizionata o reinstallata
esclusivamente da un tecnico qualificato. Un’installazione errata
può causare scosse elettriche, incendio o perdite d’acqua.
L’installazione e la messa a terra di apparecchiature elettriche
dovrebbero essere effettuate soltanto da personale qualificato
in possesso di licenza. Per ulteriori informazioni, rivolgersi al
proprio fornitore o a un tecnico installatore.
Evitare che l’unità o il suo comando remoto entrino in contatto
con l’acqua, causando scosse elettriche o fiamme.
Spegnere l’unità prima di effettuare interventi
di pulizia per evitare scosse elettriche.
In caso contrario, possono prodursi scosse elettriche e lesioni.
Per evitare scosse elettriche e incendi, installare un rilevatore
di perdite.
Non utilizzare vernice, smalto, lacca per i capelli, altri spray
infiammabili o altri liquidi che possono emettere fumi/vapori
infiammabili nelle vicinanze dell’unità, poiché ciò potrebbe
causare incendi.
In caso di sostituzione di un fusibile, assicurarsi che il fusibile
nuovo da installare sia perfettamente conforme ai requisiti.
Non aprire o rimuovere il pannello dell’unità quando questa è
accesa. Toccare i componenti interni dell’unità quando questa
è in funzione può essere causa di scosse elettriche o lesioni
causate da parti in movimento come i ventilatori.
Prima di effettuare qualsiasi intervento di riparazione o
manutenzione, assicurarsi che l’alimentazione elettrica sia
scollegata.
Non toccare mai l’unità o il suo comando remoto con le mani
umide, per evitare scosse elettriche.
Tenere l’unità fuori dalla portata dei bambini, per evitare il
rischio di lesioni. .
Non inserire le dita o altri oggetti nelle prese d’aria di ingresso e di
uscita dell’unità, per evitare lesioni o danni all’apparecchiatura.
Non vaporizzare sostanze liquide permettere infiltrazioni di
liquido nell’unità.
Non collocare vasi o altri contenitori di liquido sopra all’unità o in
luoghi da cui il liquido potrebbe gocciolare. L’acqua o altri liquidi
che possono entrare in contatto con l’unità possono causare
scosse elettriche o incendi.
Non rimuovere i rivestimenti anteriore o posteriore del comando
remoto e non toccare i componenti interni del comando
remoto, per evitare lesioni. Se il comando remoto smette di
funzionare, si prega di contattare il proprio fornitore o un tecnico
dell’assistenza qualificato.
Assicurarsi che l’unità sia collegata a terra in modo corretto. in
caso contrario, possono prodursi scosse elettriche o incendi. Le
scariche elettriche (come quelle che possono essere causate
da fulmini) possono danneggiare l’equipaggiamento elettrico.
1. Non stringere mai troppo le viti, altrimenti il coperchio potrebbe ammaccarsi o il display a cristalli liquidi rompersi.
2. Lasciare spazio sufficiente per gli interventi di manutenzione e assistenza del comando cablato.
3. Il comando cablato deve essere acquistato separatamente.
4. Seguire quanto riportato nel manuale d’uso e d’installazione del comando cablato.
Assicurasi che siano installati correttamente scaricatori e
interruttori automatici, per evitare scosse elettriche o incendi.
Smaltire l’uniin modo corretto e in conformità alle normative.
Se gli apparecchi elettrici sono smaltiti in discariche o depositi, le
sostanze pericolose possono percolare, penetrando nelle falde
acquifere ed entrando nella catena alimentare.
Non utilizzare l’unità fino a quando un tecnico qualificato non
avrà confermato che questa è sicura.
Non collocare apparecchi che producono fiamme libere nel
percorso del flusso dell’aria proveniente dall’unità. Il flusso d’aria
proveniente dall’unità può favorire la combustione, causando
un incendio e provocando lesioni gravi. Qualora il flusso
dell’aria causi una combustione incompleta, questa può
comportare una concentrazione ridotta di ossigeno nel locale,
causando gravi lesioni.
Attenzione
Utilizzare il condizionatore esclusivamente per gli scopi previsti.
Non utilizzare l’unità per refrigerare o per raffreddare cibi, piante,
animali, macchine, apparecchiature od opere d’arte.
Non inserire le dita o altri oggetti nelle prese d’aria di ingresso e
di uscita dell’unità, per evitare lesioni o danni all’apparecchiatura.
Non toccare le alette dello scambiatore di calore dell’uni
in quanto taglienti. Se toccate, possono causare lesioni. Per
evitare lesioni, in caso di interventi di riparazione, utilizzare dei
guanti o coprire lo scambiatore di calore.
Non collocare sotto l’unità oggetti che potrebbero venire
danneggiati dall’umidità. Quando l’umidità supera l’80% o il
tubo di scarico è bloccato o il filtro dell’aria è sporco, potrebbe
gocciolare dell’acqua dall’unità, danneggiando gli oggetti che si
trovassero sotto.
Accertarsi che il tubo di scarico funzioni in modo corretto. Se
il tubo di scarico è bloccato da sporco o polvere, possono
verificarsi perdite d’acqua quando l’unità è in funzione in modalità
raffreddamento. In questo caso, spegnere l’unie contattare il
fornitore o un tecnico dell’assistenza qualificato.
Non toccare le parti interne del comando. Non rimuovere il
pannello frontale. Alcuni parti interne possono causare lesioni o
venire danneggiate.
Accertarsi che bambini, piante e animali non siano esposti
direttamente al flusso dell’aria proveniente dall’unità.
Coprire l’unità e non attivarla quando si fumiga un locale con
insetticida o altre sostanze chimiche. La mancata osservanza
di questa avvertenza può portare a un deposito di sostanze
chimiche all’interno dell’unità, poi emesse da questa durante il
funzionamento, mettendo a repentaglio la salute degli occupanti
del locale.
Non smaltire il prodotto come rifiuto indifferenziato, percdeve
essere raccolto e trattato separatamente. Accertarsi che sia
rispettata la legislazione applicabile in materia di smaltimento
di refrigerante, olio e altri materiali. Contattare le autorità locali
relativamente alle informazioni e alle procedure di smaltimento.
Per evitare che si danneggi, utilizzare il comando remoto e
sostituire le batterie con cautela. Non collocare oggetti sulla sua
sommità.
Non collocare apparecchiature che presentino fiamme libere
sotto o vicino all’unità, poiché il calore potrebbe danneggiarla.
Non esporre il comando remoto dell’uni alla luce diretta del
sole. La luce diretta del sole p danneggiare il display del
comando remoto.
Non utilizzare prodotti chimici aggressivi per la pulizia dell’unità,
per evitare di danneggiare il display dell’uni o altre superfici.
Per rimuovere polvere o sporcizia dall’unità, utilizzare un panno
leggermente umido con un detergente neutro diluito. Quindi,
asciugare con un panno asciutto.
I bambini non devono giocare con l’apparecchiatura.
10
Model Power Packing Air outlet Net Static Nominal air flow
supply size(mm) dimension weight (kg) pressure (m3/h)
(mm) (Pa)
KRE 400 1360×1284×420 Φ198 71.5 100 400
74.4
KRE 800 1390×1424×540 Φ244 80 140 800
KRE 1000 220-240V1390×1670×540 Φ244 90 160 1000
KRE 1500 1830×1520×770 346×326 181.5 180 1500
Model Nominal temp. Nominal enthalpy Sound power Power input(kW) Current(A)
efficiency efficiency level(dB)
KRE 500
80.6 74.0 50 0.15 1.2
KRE 1000
82.8 76.0 54 0.38 2.9
KRE 1500
75.5 69.4 69 0.68 3.8
KRE 2000
77.2 74.7 70 0.95 5.7
10
Notes
There are 3 steps of fan speed (High, Medium, Low), all the parameters
in the above table is measured at the high speed.
Table 5-2
Table 5-1
5.
SPECIFICATION PARAMETER
5.1 Specification Parameter
5. PARAMETRO DI SPECIFICA
5.1 Parametro di specifica
Tabella 5-1
Modello
Alimentazione
Dimensione
dell'imballaggio
(mm)
Dimensione
uscita aria
(mm)
Peso
netto
(kg)
Pressione
statica
(Pa)
Flusso d'aria
nominale
(m3/h)
KRE 500D1
220-240 V~
50 Hz
1390×1244×540
Φ244
74,4
90
500
KRE 1000D1
1390×1670×540
Φ244
90
160
1000
KRE 1500D1
1830×1520×770
346×326
181,5
180
1500
KRE 2000D1
1900×1720×845
346×326
208,5
200
2000
Tabella 5-2
Modello
Efficienza
termica
nominale
Efficienza entalpica
nominale
Livello di
potenza sonora
(dB)
Potenza assorbita
(kW)
Corrente (A)
KRE 500D1
80,6
74,0
50
1,2
KRE 1000D1
82,8
76,0
54
0,38
2,9
KRE 1500D1
75,5
69,4
69
0,68
3,8
KRE 2000D1
77,2
74,7
70
0,95
5,7
Note:
Sono disponibili 3 velocità del ventilatore (alta, media e bassa); tutti i parametri della
tabella sopra sono misurati a velocità alta.
11
treatm
tempe
High e
by exh
core in
the tw
is occ
exhau
outdo
tempe
during
excha
6.2 Pay Att
Operatio
6.2.1. Befo
whe
6.2.2. Car
cont
6.2.3. Thre
the
ng Points
Before Trial Run:
8.1.1 The unit is installed correctly completed.
8.1.2 Ducting and wiring are correctly completed.
8.1.3 The drainage is smooth.
8.1.4 The heating insulation works well.
8.1.5 The ground wiring is connected correctly.
8.1.6 The power voltage fits the rated voltage of KRE.
8.1.7There is no obstacle at the outlet and inlet of KRE.
8.2 Control The KRE By Wired controller,
Operate It According To Wired controller
Owner’s Manual.
8.2.1 Whether the switch on the remote controller works well.
8.2.2 Whether the room temperature is adjusted well.
8.2.3 Whether the indicator lights normally.
8.2.4 Whether there is vibration or abnormal noise during
operation.
6.1 Operation principle
KRE (Heat Recovery Ventilation) employ advanced
technique and technics, the heat exchanged core forming
by special paper that be processed with chemical
ent, which could create the optimum result in
rature, humidity and cooling recovery.
fficiency heat exchanged core: When air flow formed
aust air and outdoor air through the heat exchanged
cross way, because of temperature difference in
o sides of flat partition board, the heat transmission
urred. In summer, outdoor air acquire cooling from air
st to decrease environment temperature; In winter,
or air acquire heat from air exhaust to increase
rature, that is to say, it realizing the energy recovery
air exhaust process to exchange the heat in heat
nged core to outdoor air.
ention To The Following Items Before
n
re start-up, please clean up the duct and check
ther all air valves and devices are normal.
efully adjust the system air valves when start-up,
rol the current of motor in rated range.
e-phase model without by-pass function, therefore
fan would delay 30 seconds to start up.
6.2.4. Connect the wired controller
Wired controller should be installed according to wired
controller owner’s manual, installation manual (Attached
in the package box in wire controller).
7.1 During early use, one should check the fan operation
regularly.
7.2 The cleaning regulation for air filter depend on local
environment. It could be clean by vacuum dirt exhauster
or water, if heavy dust accumulates, it should use neutral
detergent to clean it, and then dry it in shady and cool
place for 20 to 30 minutes and replace it.
7.3 Clean the core at least 2 years a time by vacuum dirt
exhauster to remove dust and foreign substance in the
unit assemblies, do not touch the assemblies by
exhauster and flush by water to avoid core damage.
7.4 Check the fan every half a year to maintain the well
balance of it and check whether the axletree has loosed.
6. KRE APPLICATION
7 MAINTENANCE AND UPKEEP
6. APPLICAZIONE KRE
6.1 Principio di funzionamento
L’KRE (Heat Recovery Ventilation) impiega tecniche e
tecnologie avanzate, il nucleo di scambio termico formato
con carta speciale che può essere sottoposta a trattamento
chimico, in grado di fornire risultati ottimali in termini di
temperatura, umidità e recupero di raffreddamento.
Nucleo di scambio termico ad alta efficienza: Quando
il flusso d'aria formato da aria espulsa e aria esterna
attraverso il nucleo di scambio termico in modo trasversale,
a causa della differenza di temperatura nei due lati del
pannello divisorio piano, avviene la trasmissione del calore.
In estate, l'aria esterna si raffredda per mezzo dell'aria di
scarico per diminuire la temperatura ambiente; in inverno,
l'aria esterna si scalda per mezzo dell'aria di scarico per
aumentare la temperatura, vale a dire, realizzando il
recupero di energia durante il processo di scarico dell'aria
per scambiare il calore nel nucleo di scambio termico con
l'aria esterna.
6.2 Prestare attenzione ai seguenti elementi
prima dell'uso
6.2.1. Prima dell’avviamento, pulire il condotto e controllare
se tutte le valvole dell'aria e i dispositivi sono normali.
6.2.2. Regolare con cura le valvole dell'aria dell'impianto
all'avviamento, controllare che la corrente del motore
rientri nell’intervallo nominale.
6.2.3. Modello trifase senza funzione di by-pass, quindi il
ventilatore ritarderebbe di 30 secondi l'avvio.
6.2.4. Collegare il comando cablato Il comando cablato
deve essere installato secondo il relativo manuale
d'uso e il manuale d'installazione (allegato alla
confezione del comando cablato).
7. MANUTENZIONE E MANTENIMENTO
7.1 Durante l'uso iniziale, controllare regolarmente il funzionamento
del ventilatore.
7.2 La regolazione della pulizia del filtro dell'aria dipende dall'ambiente
locale. Può essere pulito con un aspiratore o con acqua, se si
accumula molta polvere, usando un detergente neutro per poi
asciugarlo in un luogo fresco e ombreggiato per 20-30 minuti e
sostituirlo.
7.3 Pulire il nucleo almeno 2 volte l’anno con un aspiratore per
rimuovere polvere e corpi estranei nei gruppi dell'unità, non
toccare i gruppi con l'aspiratore e sciacquare con acqua per
evitare danni al nucleo.
7.4 Controllare il ventilatore ogni sei mesi per mantenerne il corretto
equilibrio e controllare se l'albero dell'asse si è allentato.
8. PROVA IN BIANCO
8.1 Confermare i seguenti punti
Prima dell'esecuzione della prova in bianco:
8.1.1 L'unità è stata installata correttamente.
8.1.2 Condotti e cablaggio sono stati completati correttamente.
8.1.3 Il drenaggio è regolare.
8.1.4 L'isolamento termico funziona bene.
8.1.5 Il cablaggio di terra è collegato correttamente.
8.1.6 La tensione di alimentazione corrisponde alla tensione
nominale dell'KRE.
8.1.7 Non sono presenti ostacoli all'uscita e all'ingresso
dell'KRE.
8.2 Controllare l’KRE per mezzo del comando
cablato, utilizzarlo conformemente al
Manuale d’uso del comando cablato.
8.2.1 Se l'interruttore sul comando remoto funziona bene.
8.2.2 Se la temperatura ambiente è stata regolata
correttamente.
8.2.3 Se l'indicatore si illumina normalmente.
8.2.4 Se ci producono vibrazioni o rumori anomali durante il
funzionamento.
12
Fan Types
Centrifugal forward curved fan
Directive (or Standard) for Regulation ErP Directive 2009/125/EC
COMMISSION REGULATION (EU) No 327/2011
Model Name
WZDK170-38G-2 +LX-245*203*12- Rev.
48J 1320
Prepare by
No.
Information Item
Comment
1 ηtarget= 32.5%
2 Overall efficiencye(ηe )= 33.02%
3 Pass or not (Criteria:ηeηtarget) Pass
4 Measurement category (A -D) A
5 Efficiency category (static or total) Static
6 Efficiency grade at optimum energy efficiency point N =44.52
7 VSD is integrated within the fan YES
8 Year of Manufacture Ref. to the Unit Nameplate
9 Manufacturer’s name and place of manufacture Ref. to the Unit Nameplate
Rated motor power input(s) (kW), at optimum energy
10.1 efficiency 0.1517 kw
10.2 Rated motor flow rate(s) at optimum energy efficiency 0.1614m3/s
10.3 Rated motor pressure(s) at optimum energy efficiency 270 Pa
Rotations per minute (R.P.M)at the optimum energy
11 efficiency point 1320r/min
12 Specific ratio 1.001
13 Information relevant for facilitating disassembly, all materials can be recycled
recycling or disposal at end-of-life
Information relevant to minimize impact on the For installation, the clearance of
14 environment and ensure optimal life expectancy as 500 mm shall be kept from inlet
regards installation, use and maintenance of the fan
Description of additional items used when determining Measurement category A, fan is free
15 the fan energy efficiency,such as ducts, that are not inlet and outlet conditions
described in the measurement category and supplied
with the fan.
16 Motor manufacturer NIDEC
SHIBAURA(ZHEJIANG)CORP.
Specified Information of Fan:
9.INFORMAZIONI SULL’ERP
Tabella. 9-1
Tipi di ventilatore
Ventilatore centrifugo a pale avanti
Direttiva (o norma) per regolamento
Direttiva ErP 2009/125/CE
REGOLAMENTO (UE) N. 327/2011 DELLA
COMMISSIONE
Nome del modello
WZDK170-38G-2 +LX-245*203*12-
48J 1320
Rev.
Preparato da
Informazioni specifiche del ventilatore:
N.
Informazioni articolo
Commento
1
ηtarget=
32,5%
2
Efficienza complessiva e )=
33,02%
3
Passa o no (Criteri: ηe ≥ ηtarget)
Passa
4
Categoria di misura (A -D)
A
5
Categoria di efficienza (statica o totale)
Statica
6
Grado di efficienza al punto ottimale di efficienza
energetica
N =44,52
7
VSD integrato nel ventilatore
8
Anno di produzione
Rif. alla targhetta dati dell'unità
9
Nome del fabbricante e luogo di fabbricazione
Rif. alla targhetta dati dell'unità
10.1
Potenza nominale assorbita dal motore (kW), con
efficienza energetica ottimale
0,1517 kw
10.2
Portata nominale del motore con efficienza energetica
ottimale
0,1614 m3/s
10.3
Pressione nominale del motore con efficienza energetica
ottimale
270 Pa
11
Rotazioni al minuto (R.P.M.) nel punto di efficienza
energetica ottimale
1320 r/min
12
Rapporto specifico
1,001
13
Informazioni utili per facilitare lo smontaggio, il riciclaggio
o lo smaltimento a fine vita
tutti i materiali possono essere
riciclati
14
Informazioni utili per ridurre al minimo l'impatto
ambientale e garantire una durata di vita ottimale per
quanto riguarda l'installazione, l'uso e la manutenzione del
ventilatore
Per l'installazione, deve essere
mantenuto uno spazio libero di 500
mm dall'ingresso
15
Descrizione degli elementi aggiuntivi utilizzati per
determinare l'efficienza energetica dei ventilatori, come i
condotti, che non sono descritti nella categoria di misura e
forniti con il ventilatore.
Categoria di misura A, ingresso e
uscita ventilatore libere
16
Produttore del motore
NIDEC SHIBAURA(ZHEJIANG)
CORP.
13
Fan Types Centrifugal forward curved fan
Directive (or Standard) for Regulation ErP Directive 2009/125/EC
COMMISSION REGULATION (EU) No 327/2011
Model Name WZDK750-38G-W-1+LX-261*234*15 Rev.
-48J 1300
Prepare by
No.
Information Item
Comment
1 ηtarget= 34.14%
2 Overall efficiencye(ηe )= 49.7%
3 Pass or not (Criteria:ηeηtarget) Pass
4 Measurement category (A -D) A
5 Efficiency category (static or total) Static
6 Efficiency grade at optimum energy efficiency point N =59.51
7 VSD is integrated within the fan YES
8 Year of Manufacture Ref. to the Unit Nameplate
9 Manufacturer’s name and place of manufacture Ref. to the Unit Nameplate
10.1 Rated motor power input(s) (kW), at optimum energy
efficiency 0.276 kw
10.2 Rated motor flow rate(s) at optimum energy efficiency 0.34m3/s
10.3 Rated motor pressure(s) at optimum energy efficiency 360 Pa
11 Rotations per minute (R.P.M)at the optimum energy
1300r/min
efficiency point
12 Specific ratio 1.001
13 Information relevant for facilitating disassembly, All materials can be recycled
recycling or disposal at end-of-life
Information relevant to minimize impact on the For installation,the clearance of
14 environment and ensure optimal life expectancy as 500 mm shall be kept from inlet
regards installation, use and maintenance of the fan
Description of additional items used when determining
15 the fan energy efficiency,such as ducts, that are not Measurement category A, fan is free
described in the measurement category and supplied inlet and outlet conditions
with the fan.
16 Motor manufacturer Panasonic Appliances
Motor(Hangzhou)Co.Ltd.
Specified Information of Fan:
Tipi di ventilatori Ventilatore centrifugo a pale avanti
Direttiva (o norma) per regolamento
Direttiva ErP 2009/125/CE
REGOLAMENTO (UE) N. 327/2011 DELLA
COMMISSIONE
Nome del
modello
WZDK750-38G-W-1+LX-261*234*15
-48J 1300
REV.
Preparato da
Informazioni specifiche del ventilatore:
N.
Informazioni articolo
Commento
1
ηtarget=
34,14%
2
Efficienza complessiva e )=
49,7%
3
Passa o no (Criteri: ηe ≥ ηtarget)
Passa
4
Categoria di misura (A -D)
A
5
Categoria di efficienza (statica o totale)
Statica
6
Grado di efficienza al punto ottimale di efficienza
energetica
N =59,51
7
VSD integrato nel ventilatore
8
Anno di produzione
Rif. alla targhetta dati dell'unità
9
Nome del fabbricante e luogo di fabbricazione
Rif. alla targhetta dati dell'unità
10.1
Potenza nominale assorbita dal motore (kW), con
efficienza energetica ottimale
0,276 kw
10.2
Portata nominale del motore con efficienza energetica
ottimale
0,34 m3/s
10.3
Pressione nominale del motore con efficienza energetica
ottimale
360 Pa
11
Rotazioni al minuto (R.P.M.) nel punto di efficienza
energetica ottimale
1300 r/min
12
Rapporto specifico
1,001
13
Informazioni utili per facilitare lo smontaggio, il riciclaggio
o lo smaltimento a fine vita
Tutti i materiali possono essere
riciclati
14
Informazioni utili per ridurre al minimo l'impatto
ambientale e garantire una durata di vita ottimale per
quanto riguarda l'installazione, l'uso e la manutenzione del
ventilatore
Per l'installazione, deve essere
mantenuto uno spazio libero di 500
mm dall'ingresso
15
Descrizione degli elementi aggiuntivi utilizzati per
determinare l'efficienza energetica dei ventilatori, come i
condotti, che non sono descritti nella categoria di misura e
forniti con il ventilatore.
Categoria di misura A, ingresso e
uscita ventilatore libere
16
Produttore del motore
Panasonic Appliances
Motor(Hangzhou)Co.Ltd.
Tabella. 9-2
14
No.
Information Item
Comment
1 Supplier's name
2 Model name KRE-2B-Mi KRE-2B-Mi KRE-2B-Mi KRE 500
KRE 1000D1 D1500 KRE
2000D1
3 Declared typology
NRVU,BVU NRVU,BVU NRVU,BVU NRVU,BVU
4 Type of drive Multi-speed Multi-speed Multi-speed Multi-speed
5 Type of HRS Other Other Other Other
6 Thermal efficiency(%) 80.6 82.8 75.5 77.2
7 Nominal
flow
rate(m
/s)
3 0.139 0.278 0.417 0.556
8 Electric power input(kW) 0.157 0.383 0.677 0.956
9
SFPint(W/(m
3
/h))
682 785 702 730
10 Face velocity(m/s) 0.66 0.87 1.0 1.0
11 Nominal external pressure(Pa) 96 160 180 200
12 Internal pressure drop(Pa) 90 145 159 185
13 Internal pressure drop of - - - -
non-ventilation components(Pa)
14 Efficiency in Regulation (EU) Out of scope 33 49.7 49.7
NO 327/2011
15 Maximum leakage rate(%) 10 0r less 10 0r less 10 0r less 10 0r less
Energy classification of the
16 filters - - - -
17 Visual filter warning
18 Casingsound power level(dB) 50 54 69 70
19 Internet address for disassembly
instructions
Required information for NRVU in COMMISSION REGULATION (EU) No.1253/2014 ANNEX V
Table 12-4
Informazioni richieste per l'NRVU nel REGOLAMENTO (UE) N. 1253/2014 ALLEGATO V
Tabella 12-4
N.
Informazioni articolo
Commento
1
Nome del fornitore
2
Nome del modello
KRE 500D1
KRE 1000D1
KRE 1500D1
KRE 2000D1
3
Tipologia dichiarata
NRVU, BVU
NRVU, BVU
NRVU, BVU
NRVU, BVU
4
Tipo di unità
Multi-
velocità
Multi-
velocità
Multi-
velocità
Multi-velocità
5
Tipo di HRS
Altro
Altro
Altro
Altro
6
Efficienza termica (%)
80,6
82,8
75,5
77,2
7
Portata d'aria nominale (m 3/s)
0,139
0,278
0,417
0,556
8
Potenza elettrica assorbita (kW)
0,157
0,383
0,677
0,956
9
SFPint(W/(m
3
/h))
682
785
702
730
10
Velocità di flusso (m/s)
0,66
0,87
1,0
1,0
11
Pressione esterna nominale (Pa)
96
160
180
200
12
Perdita di carico interna (Pa)
90
145
159
185
13
Perdita di carico interna
dei componenti non ventilati (Pa)
-
-
-
-
14
Efficienza nel regolamento (UE) n.
327/2011
Fuori dal
campo di
applicazione
33
49,7
49,7
15
Tasso massimo di perdita (%)
10 o
inferiore
10 o
inferiore
10 o
inferiore
10 o
inferiore
16
Classificazione energetica dei filtri
-
-
-
-
17
Avviso visivo del filtro
Fare riferimento al libretto di istruzioni
18
Livello di potenza sonora
dell'involucro (dB)
50
54
69
70
Tabella. 9-4
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20

Kaysun KRE Manuale utente

Categoria
Condizionatori d'aria a sistema split
Tipo
Manuale utente

in altre lingue