Sonel TKF-13 Manuale utente

Categoria
Misurazione
Tipo
Manuale utente
1
INSTRUKCJA OBSŁUGI 1
USER MANUAL 7
MANUAL DE USO 13
BEDIENUNGSANLEITUNG 19
MANUALE D'USO 25
РУКОВОДСТВО ПО ЭКСПЛУАТАЦИИ 31
TKF-13
v2.01 03.07.2023
1
INSTRUKCJA OBSŁUGI
TESTER KOLEJNOŚCI FAZ I KIERUNKU
OBROTÓW SILNIKA
TKF-13
SONEL S.A.
ul. Wokulskiego 11
58-100 Świdnica
Wersja 2.01 03.07.2023
TKF-13 INSTRUKCJA OBSŁUGI
2
SPIS TREŚCI
1 Bezpieczeństwo ........................................................................................................................... 2
2 Test kierunku wirowania faz ....................................................................................................... 3
3 Test kierunku wirowania wału silnika (przewodowy) ................................................................ 3
4 Test kierunku wirowania wału silnika (bezprzewodowy) .......................................................... 4
5 Wyłączenie zasilania ................................................................................................................... 5
6 Sygnalizacja stanu baterii ........................................................................................................... 5
7 Wymiana baterii ........................................................................................................................... 5
8 Czyszczenie i konserwacja ......................................................................................................... 5
9 Magazynowanie ........................................................................................................................... 5
10 Rozbiórka i utylizacja .................................................................................................................. 5
11 Dane techniczne .......................................................................................................................... 6
12 Producent..................................................................................................................................... 6
Dziękujemy za zakup naszego testera kolejności faz i kierunku obrotów silnika. Tester TKF-13 jest nowocze-
snym, wysokiej jakości przyrządem, łatwym i bezpiecznym w obsłudze. Jednak przeczytanie niniejszej instrukcji
pozwoli uniknąćędów podczas testów i zapobiegnie ewentualnym problemom przy obsłudze przyrządu.
Producent zastrzega sobie prawo wprowadzania zmian w wyglądzie, wyposażeniu i danych
technicznych przyrządu.
1 Bezpieczeństwo
Przyrząd TKF-13 odpowiada wymaganiom bezpieczeństwa wg normy PN-EN 61010-1.
Dla bezpieczeństwa własnego i przyrządu należy przestrzegać zasad opisanych w tej instrukcji.
Ostrzeżenia:
Nie sprawdzaj obiektów w środowisku zawilgoconym, za-
wierającym gazy (materiały) wybuchowe lub łatwopalne, pa-
rę wodną lub kurz.
Po przeniesieniu przyrządu ze środowiska zimnego do cie-
ego odczekaj przed użyciem 0,5 h w celu aklimatyzacji, w
razie potrzeby wytrzyj skroploną parę wodną.
Podczas pomiarów nie dotykaj części metalowych gniazd-
ka, końcówek przewodów, elementów mocujących, obwo-
dów itp.
Zapewnij sobie dobrą izolację od testowanego obiektu.
Nie wykonuj pomiarów przyrządem niesprawnym, z uszko-
dzoną obudową lub przewodami (nadłamania, pęknięcia, deformacje, zanieczyszczenie itp.).
Przyrząd TKF-13 może być używany jedynie przez wykwalifikowane osoby posiadające odpowiednie
uprawnienia do prac przy instalacjach elektrycznych. Posługiwanie sprzyrządem przez osoby nieu-
prawnione może spowodowuszkodzenie przyrządu i być źródłem poważnego niebezpieczeństwa dla
użytkownika.
Tester można podłączyć do sieci energetycznej tylko za pomocą dedykowanych przewodów dostarczo-
nych przez producenta. Tylko takie przewody gwarantują zgodność z przepisami bezpieczeństwa.
Podłączenie do testera napięcia większego niż 760 V może spowodować jego uszkodzenie i zagroże-
nie dla użytkownika.
Każde inne zastosowanie przyrządu niż podane w tej instrukcji może spowodowjego uszkodzenie
i być źródłem poważnego niebezpieczeństwa dla użytkownika.
TKF-13 INSTRUKCJA OBSŁUGI
3
2 Test kierunku wirowania faz
Naciskając uruchomić tester. Powinna zapalić się zielona
dioda ON sygnalizująca gotowość przyrządu do pracy.
Podłączyć sondy pomiarowe do testera TKF-13.
Podłączyć sondy pomiarowe do punktów, gdzie występuje spo-
dziewane napięcie trójfazowe (obok przykładowy rysunek).
Jeśli fazy w danych punktach pomiarowych zgodne z opisem
L1, L2, L3 na testerze zaświeca się dioda R, w przeciwnym wy-
padku dioda L.
Świecenie danej neonówki (L1, L2, L3) sygnalizuje istnienie napię-
cia większego niż 100 V między odpowiadającą jej sondą, a którąś
z pozostałych sond.
Błędne wskazania mogą być powodowane przez:
podłączenie dwóch sond do jednej fazy,
podłączenie jednej z sond do przewodu neutralnego,
brak podłączenia którejś z sond do sieci energetycznej.
3 Test kierunku wirowania wału silnika (przewodowy)
Odłączyć silnik od sieci energetycznej.
Naciskając uruchomić tester. Powinna zapalić się zielona
dioda ON sygnalizująca gotowość przyrządu do pracy.
Podłączyć sondy pomiarowe do testera TKF-13.
Podłączyć sondy pomiarowe do badanego silnika (patrz rysunek ob-
ok).
Energicznie zakręcić wałem silnika w pożądanym kierunku.
Świecenie diody R oznacza, że podłączenie do zacisków silnika
U, V, W odpowiednio faz L1, L2, L3, będzie skutkowało wirowaniem
silnika w kierunku, w jakim obracany był wał w czasie testu.
Świecenie diody L oznacza, że podłączenie do zacisków silnika
U, V, W odpowiednio faz L1, L2, L3, będzie skutkowało wirowaniem
wału silnika w przeciwnym kierunku, do tego w jakim obracany był w
czasie testu.
Aby mieć pewność, że po podłączeniu silnika do zasilania jego wał
będzie obracał się w żądanym kierunku, należy przeprowadzić test
kolejności faz (patrz rozdział 1).
TKF-13 INSTRUKCJA OBSŁUGI
4
4 Test kierunku wirowania wału silnika (bezprzewodowy)
Naciskając uruchomić tester. Powinna zapalić się zielona
dioda ON sygnalizująca gotowość przyrządu do pracy.
Przyłożyć tylną część testera TKF-13 do pracującego silnika wzdłuż
jego osi (położenie osi zgodnie z rysunkiem obok). Odległość od te-
stera do silnika nie powinna być większa niż 2-3 cm.
Świecenie diody R oznacza, że wał silnika obraca się zgodnie z kie-
runkiem ruchu wskazówek zegara. Świecenie diody L oznacza, że
wał wiruje przeciwne.
Brak wskazań (diody L i R wygaszone) może oznaczać nie pracujący
silnik lub zbyt słaby sygnał.
W przypadku niektórych silników indukcyjnych jednofazo-
wych, wskazania mogą być utrudnione.
Przyrząd nie jest przeznaczony do badania silników jedno-
fazowych komutatorowych.
Przyrząd nie jest przeznaczony do badania silników zasila-
nych przez przekształtniki energoelektroniczne (falowniki).
Poniżej przedstawiono wykres ilustrujący minimalną średnicę silnika dla danych obrotów i częstotliwo-
ści sieci energetycznej, przy której wskazania testera są wiarygodne.
0
10
20
30
40
50
60
70
80
90
0500 1000 1500 2000 2500 3000 3500 4000
obroty/min
minimalna średnica silnika [cm]
16.66 Hz
50Hz
60Hz
TKF-13 INSTRUKCJA OBSŁUGI
5
5 Wyłączenie zasilania
Jeśli w ciągu pięciu minut nie zaświeci się dioda L lub R, następuje automatyczne wyłączenie te-
stera, dioda ON gaśnie.
Nie ma możliwości ręcznego wyłączenia zasilania.
6 Sygnalizacja stanu baterii
Jeśli tester wykryje, że w baterii pozostało około 10% energii, dioda stanu baterii zaczyna
pulsować co 1 s. Pomiary są nadal możliwe.
Jeśli bateria jest wyczerpana, dioda stanu baterii świeci światłem ciągłym i niemożliwe
jest wykonywanie pomiarów. W tym momencie należy wymienić baterie. Jeśli bateria nie zo-
stanie wymieniona, po pięciu minutach nastąpi automatyczne wyłączenie testera.
7 Wymiana baterii
Odłączyć sondy pomiarowe od sieci energetycznej.
Ściągnąć z obudowy elastyczną osłonę.
Odkręcić tylną dolną część obudowy, a następnie wyciągnąć ją.
Wyjąć baterię z testera, a następnie odłączyć ją.
Podłączyć nową baterię, przykręcić tylną klapkę i naciągnąć elastyczną osłonę na obudowę.
8 Czyszczenie i konserwacja
UWAGA!
Należy stosować jedynie metody konserwacji podane przez producenta w niniejszej in-
strukcji.
Tester można czyścić miękką, wilgotną flanelą używając ogólnie dostępnych detergentów.
Nie należy używać żadnych rozpuszczalników, ani środków czyszczących, które mogłyby poryso-
wać obudowę (proszki, pasty itp.).
Układ elektroniczny testera nie wymaga konserwacji.
9 Magazynowanie
Przy przechowywaniu testera należy przestrzegać poniższych zaleceń:
upewnić się, że tester jest suchy,
przy dłuższym okresie przechowywania, należy wyjąć baterię z testera.
10 Rozbiórka i utylizacja
Zużyty sprzęt elektryczny i elektroniczny należy gromadzić selektywnie, tj. nie umieszczać z od-
padami innego rodzaju.
Zużyty sprzęt elektroniczny należy przekazać do punktu zbiórki zgodnie z ustawą o zużytym
sprzęcie elektrycznym i elektronicznym.
Przed przekazaniem sprzętu do punktu zbiórki nie należy samodzielnie demontować żadnych
części z tego sprzętu.
Należy przestrzegać lokalnych przepisów dotyczących wyrzucania opakowań, zużytych baterii
i akumulatorów.
TKF-13 INSTRUKCJA OBSŁUGI
6
11 Dane techniczne
a) rodzaj izolacji zgodnie z PN-EN 61010-1 .......................................................................... podwójna
b) kategoria pomiarowa wg PN-EN 61010-1 ........................................................................... III 600 V
c) stopień ochrony obudowy wg PN-EN 60529 ............................................................................ IP42
d) zakres częstotliwości ........................................................................................................ 2 ÷ 70 Hz
e) zakres międzyfazowych napięć roboczych.............................................................. 120 ÷ 760 V AC
f) zakres międzyfazowych napięć nominalnych ........................................................... 127÷ 690 V AC
g) zakres napięć SEM silników ....................................................................................... 1 ÷ 760 V AC
h) prąd pomiarowy (na każdą fazę) ......................................................................................... <3,5 mA
i) temperatura pracy .......................................................................................................... -10 ÷ 45ºC
j) temperatura przechowywania ......................................................................................... -20 ÷ 60ºC
k) okres migania diody stanu baterii ........................................................................................... ok. 1 s
l) czas do automatycznego wyłączenia ................................................................................. ok. 5 min
m) zasilanie testera................................................................................ bateria alkaliczna 6LR61 (9 V)
n) wymiary ............................................................................................................... 130 x 72 x 31 mm
o) masa ................................................................................................................................. ok. 150 g
Urządzenie nie posiada charakteru wzorca i dlatego nie podlega wzorcowaniu. a-
ściwą formą kontroli dla tego typu przyrządów jest sprawdzenie.
12 Producent
Producentem przyrządu prowadzącym serwis gwarancyjny i pogwarancyjny jest:
SONEL S.A.
ul. Wokulskiego 11
58-100 Świdnica
tel. +48 74 884 10 53 (Biuro Obsługi Klienta)
e-mail: bok@sonel.pl
internet: www.sonel.pl
UWAGA!
Do prowadzenia napraw serwisowych upoważniony jest jedynie producent.
7
USER MANUAL
PHASE SEQUENCE AND MOTOR
ROTATION DIRECTION TESTER
TKF-13
SONEL S.A.
Wokulskiego 11
58-100 Świdnica
Poland
Version 2.01 03.07.2023
TKF-13 USER MANUAL
8
CONTENTS
1 Safety ........................................................................................................................................... 8
2 Phase rotation direction test....................................................................................................... 9
3 Motor shaft rotation direction (using leads) .............................................................................. 9
4 Motor shaft rotation direction (connectionless) ...................................................................... 10
5 Power supply turn-off ................................................................................................................ 11
6 Battery charge signalling .......................................................................................................... 11
7 Replacement of batteries .......................................................................................................... 11
8 Cleaning and maintenance ....................................................................................................... 11
9 Storage ....................................................................................................................................... 11
10 Dismantling and utilization ....................................................................................................... 11
11 Technical data............................................................................................................................ 12
12 Manufacturer .............................................................................................................................. 12
We appreciate your having purchased our phase sequence and motor rotation direction tester. The TKF-13
tester is a modern high-quality, simple and safe device. However it is recommended to get acquainted with
the present manual in order to avoid measuring errors and prevent possible problems related to operation of
the meter.
The manufacturer reserves the right to modify the appearance, equipment and technical da-
ta of the device.
1 Safety
The TKF-13 tester complies with the safety requirements specified in the norm EN 61010-1.
In order to protect yourself and the device do observe the rules described in the present manual.
Warning:
Do not perform tests in a humid environment, which contains
explosive or inflammable gases (materials), water vapour or
dust.
Having carried the device from a cold environment to a warm
one, wait 0.5 hour before you proceed to perform measure-
ments for the purpose of acclimatisation, if necessary wipe
out the condensed water vapour.
During measurements do not touch the metal parts of the
socket, lead terminals, fastening elements, circuits, etc.
Make sure you are properly insulated from the tested object.
Do not perform measurements using an out-of-order device, whose casing or leads are damaged (bro-
ken, cracked, deformed, contaminated, etc.).
The TKF-13 tester may be operated exclusively by qualified personnel who are properly authorised to
perform work on electric installations. Should the device be operated by unauthorised personnel, the
device may be damaged and there may be a serious danger for the operator.
The tester may be connected to the mains solely by means of dedicated leads provided by the manu-
facturer. Solely such leads guarantee compliance with safety regulations.
If phase-to-phase voltage exceeding 760 V AC will be connected to the device, the tester may be dam-
aged and there may be a risk for the operator.
If the device will be used for any other purpose than those specified in the present operating manual,
the tester may be damaged and there may be a serious risk for the operator.
TKF-13 USER MANUAL
9
2 Phase rotation direction test
Press to turn the tester on. The green diode should go ON
signalling that the device is ready for operation.
Connect measurement probes to the TKF-13 tester.
Connect measurement probes to the points where there is the ex-
pected three-phase voltage (see the illustration below).
If the phases at the given measurement points are compliant with
the L1, L2, L3 description, the R diode of the tester will go on;
otherwise the L diode will go on.
The light of the given neon lamp (L1, L2, L3) signalises a voltage
exceeding 100 V between the corresponding probe and one of the
remaining probes.
Incorrect indications of the tester may be caused by one of
the following:
connection of two probes to one phase,
connection of one of the probes to the neutral lead,
lack of connection of one of the probes to the mains.
3 Motor shaft rotation direction (using leads)
Disconnect the motor from the mains.
Press to turn the tester on. The green diode should go ON
signalling that the device is ready for operation.
Connect measurement probes to the TKF-13 tester.
Connect measurement probes to the tested motor (see the adja-
cent illustration).
Rotate the motor shaft energetically in the desired direction.
The light of the R diode means the connection to the U, V and W
motor terminals of phases L1, L2 and L3, respectively, will cause
rotation of the motor in the direction the shaft spun during the test.
The light of the L diode means the connection to the U, V and W
motor terminals of phases L1, L2 and L3, respectively, will cause
rotation of the motor in the opposite direction to the direction the
shaft spun during the test.
Make sure the shaft rotates in the desired direction once the mo-
tor has been connected to the power supply source performing a
phase sequence test (see Chapter 2).
TKF-13 USER MANUAL
10
4 Motor shaft rotation direction (connectionless)
Press to turn the tester on. The green diode should go ON
signalling that the device is ready for operation.
Put the rear part of the TKF-13 tester to a working motor along its
axis (the position of the axis in accordance with the adjacent illus-
tration). The distance between the tester and the motor should not
exceed 2-3 cm.
The light of the R diode means the motor shaft spins clockwise.
The light of the L diode means the motor shaft spins anticlock-
wise.
Lack of indications (diodes L and R are off) may mean the motor
is not working or the signal is too weak.
In case of certain single-phase inductive motors, indica-
tions may be hindered.
The device has not been designed for the purpose of
tests of single-phase commutator motors.
The device has not been designed for the purpose of
tests of motors powered through electronic power con-
verters (inverters).
Below there is a diagram illustrating the minimum motor diameter for the given revolution and the fre-
quency of the mains at which the indications of the tester are reliable.
0
10
20
30
40
50
60
70
80
90
0
500
1000
1500
2000
2500
3000
3500
4000
rpm
minimum motor diameter [cm]
16.66 Hz
50 Hz
60 Hz
TKF-13 USER MANUAL
11
5 Power supply turn-off
If within five minutes the L or R diode does not go on, the tester is automatically turned off, and
the ON diode goes off.
It is not possible to turn the power supply off manually.
6 Battery charge signalling
When the tester detects the battery charge amounts to 10% of its full charge, the battery charge
diode starts to blink once a second. Measurements are still possible.
If the battery is discharged, then the battery charge diode is it continuously and it is im-
possible to perform measurements. It is necessary to replace batteries. If the battery is not re-
placed, then after five minutes the tester will be automatically turned off.
7 Replacement of batteries
Disconnect the measurement probes from the mains.
Remove the elastic protection from the casing.
Unscrew the rear part of the casing and remove it.
Remove the battery from the tester and disconnect it.
Connect a new battery, screw the rear flap and place the elastic protection upon the casing.
8 Cleaning and maintenance
NOTE!
Use solely the maintenance techniques specified by the manufacturer in this user
manual.
The tester may be cleaned with a soft, damp cloth using all-purpose detergents.
Do not use any solvents or cleaning agents which might scratch the casing (powders, pastes, etc.).
The electronic system of the meter does not require maintenance..
9 Storage
In the case of storage of the device, the following recommendations must be observed:
Make sure the tester is dry.
Should the tester be stored for a prolonged period of time, the battery will be removed.
10 Dismantling and utilization
Worn-out electric and electronic equipment should be gathered selectively, i.e. it must not be
placed with waste of another kind.
Worn-out electronic equipment should be sent to a collection point in accordance with the law of
worn-out electric and electronic equipment.
Before the equipment is sent to a collection point, do not dismantle any elements.
Observe the local regulations concerning disposal of packages, worn-out batteries and rechargea-
ble batteries.
TKF-13 USER MANUAL
12
11 Technical data
a) Type of insulation in accordance with EN 61010-1 ................................................................. double
b) Measurement category in accordance with EN 61010-1 ..................................................... III 600 V
c) Ingress protection in accordance with EN 60529 .................................................................... IP42
d) Frequency range .............................................................................................................. 2 ÷ 70 Hz
e) Nominal phase-to-phase voltage range .................................................................. 127 ÷ 690 V AC
f) Phase-to-phase working voltage range ................................................................... 120 ÷ 760 V AC
g) Motor voltage range .................................................................................................... 1 ÷ 760 V AC
h) Measurement current (per each phase) .............................................................................. <3.5 mA
i) Working temperature ...................................................................................................... -10 ÷ 45ºC
j) Storage temperature ....................................................................................................... -20 ÷ 60ºC
k) Battery charge diode blinking rate ......................................................................... approximately 1 s
l) Time before automatic turn-off .......................................................................... approximately 5 min
m) Tester power supply ............................................................................. alkaline battery 6LR61 (9 V)
n) Dimensions .......................................................................................................... 130 x 72 x 31 mm
o) Mass of the tester (with battery, without leads) .................................................................. ca. 150 g
The device does not have the character of a standard and therefore is not subject to
calibration. The proper form of control for this type of instrument is checking.
12 Manufacturer
The manufacturer of the device and provider of guarantee and post-guarantee service:
SONEL S.A.
Wokulskiego 11
58-100 Świdnica
Poland
tel. +48 74 884 10 53 (Customer Service)
e-mail: customer[email protected]
web page: www.sonel.com
NOTE!
Service repairs must be performed only by the manufacturer.
13
MANUAL DE USO
COMPROBADOR DE SECUENCIA
DE FASES Y SENTIDO DE GIRO
DE MOTORES
TKF-13
SONEL S.A.
Wokulskiego 11
58-100 Świdnica
Polonia
Versión 2.01 03.07.2023
TKF-13 MANUAL DE USO
14
ÍNDICE
1 Seguridad ................................................................................................................................... 14
2 Prueba de dirección de rotación de fases ............................................................................... 15
3 Prueba de sentido de giro del eje del motor (con conexión de cable) .................................. 15
4 Prueba del sentido de giro ........................................................................................................ 16
5 Desconexión .............................................................................................................................. 17
6 Indicación estado de la batería ................................................................................................. 17
7 Cambio de la batería .................................................................................................................. 17
8 Limpieza y mantenimiento ........................................................................................................ 17
9 Almacenamiento ........................................................................................................................ 17
10 Desmontaje y utilización ........................................................................................................... 17
11 Datos técnicos ........................................................................................................................... 18
12 Fabricante .................................................................................................................................. 18
Gracias por comprar nuestro probador de secuencia de fases y sentido de giro de motores. El TKF-13 es un
dispositivo moderno, de alta calidad, fácil y seguro de usar. Lea estas instrucciones para evitar errores de
medición y prevenir posibles problemas relacionados con el funcionamiento del dispositivo.
El fabricante se reserve el derecho de hacer cambios en la apariencia y características del
equipo.
1 Seguridad
El equipo TKF-13 cumple con los requisitos de seguridad de acuerdo con la normativa EN 61010-1.
Por su propia seguridad y del dispositivo debe seguir las normas descritas en este manual.
Advertencias:
No compruebe los objetos en un ambiente húmedo, que
contenga gases, (o materiales), explosivos o inflamables,
vapor o polvo.
Después de desplazar el dispositivo del entorno frío al
caliente hay que esperar 0,5 horas antes de su uso con el
fin de aclimatarse, si es necesario limpie el agua
condensada.
Durante las mediciones, no toque las partes metálicas del
enchufe, extremos de los cables, componentes de montaje ,
circuitos, etc.
Asegúrese de tener un buen aislamiento del objeto bajo
prueba.
No realice mediciones del dispositivo que no funciona, con la cubierta dañada o cables (rotos, con
grietas, deformaciones, contaminación, etc).
El dispositivo TKF-13 puede ser utilizado sólo por personas cualificadas que estén facultadas para
trabajar con instalaciones eléctricas. El uso del dispositivo por personas no autorizadas puede
peligroso para las personas y bienes.
El comprobador se puede conectar a la red sólo a través de los cables suministrados por el fabricante.
Sólo estos cables garantizan el cumplimiento con las normas de seguridad.
No conetar a tensiónes superiores a 760 V; pueden dañar al equipo y al usuario.
TKF-13 MANUAL DE USO
15
2 Prueba de dirección de rotación de fases
Pulsar para encender el TKF-13, se encenderá el diodo verde
ON.
Conectar los cables de medición al comprobador TKF-13.
Conectar los cables de medición a los puntos donde se encuentra
la tensión trifásica (ver dibujo).
Si las fases de los puntos de medición coinciden con la
descripción L1, L2, L3 en el comprobador se enciende el diodo R,
en caso contrario se enciende el diodo L.
La iluminación de las lámparas de neón (L1, L2, L3) indica la
existencia de una tensión superior a 100 V entre la fase
correspondiente, y cualquiera de las otras fases.
Una indicación incorrecta puede ser causada por:
conexión de dos cables a una fase.
conexión de uno de los cables al neutro,
no conexión de los cables a la red eléctrica.
3 Prueba de sentido de giro del eje del motor
(con conexión de cable)
Desconectar el motor de la red eléctrica.
Pulsar se encenderá el diodo verde ON.
Conectar los cables de medición al TKF-13.
Conectar los cables de medición al motor a probar (ver dibujo).
Girar enérgicamente el eje del motor en la dirección deseada.
Si el diodo R se ilumina, significa que la conexión a los terminales
del motor U, V, W, respectivamente a las fases L1, L2, L3, dará
como resultado que el motor gire en la dirección en la que el eje
fue rotado durante la prueba.
Si el diodo L se ilumina, significa que la conexión a los terminales
del motor U, V, W, respectivamente a las fases L1, L2, L3, dará
como resultado que el motor gire en la dirección contraria en la
que el eje fue rotado durante la prueba.
Para estar seguro de que cuando se conecte el motor a la
alimentación el eje gire en la dirección deseada, debe realizarse
tambien prueba de la secuencia de fases (ver el capítulo 1).
TKF-13 MANUAL DE USO
16
4 Prueba del sentido de giro
Pulsar , se encenderá el diodo verde ON.
Ponga la parte posterior del probador TKF-13 al motor en marcha
a lo largo de su eje (posición del eje según dibujo). La distancia
desde el comprobador hasta el motor no debe ser superior a 2 ó
3 cm.
Si el diodo R esta encendido, significa que el eje del motor gira en
sentido horario. Si el diodo L está encendido, significa que el eje
gira en dirección contraria.
Si no hay indicaciones (los iodos L y R estan apagados), puede
significar que el motor no está trabajando o la señal es muy débil.
Para algunos motores de inducción monofásica, las
indicaciones pueden ser difíciles.
El dispositivo no está diseñado para probar los motores
de colector de una sola fase.
El dispositivo no está diseñado para probar los motores
alimentados por convertidores electrónicos (inversores).
A continuación se muestra un gráfico que ilustra el diámetro mínimo del motor según la rotación y la
frecuencia de red en la que hay indicaciones fiables del comprobador.
0
10
20
30
40
50
60
70
80
90
0
500
1000
1500
2000
2500
3000
3500
4000
rpm
diámetro mínimo del motor [cm]
16,66 Hz
50 Hz
60 Hz
TKF-13 MANUAL DE USO
17
5 Desconexión
Si transcurridos cinco minutos, los diodos L o R no se encienden, el comprobador se apaga
automáticamente, el diodo ON se apaga.
No es posible apagar manualmente el equipo.
6 Indicación estado de la batería
Cuando el comprobador detecta que de las baterías estan aproximadamente al 10% de la carga,
el diodo de estado de la batería comienza a parpadear cada 1s. Las medidas aún son
posibles.
Si la batería está agotada, el diodo de estado de la batería se ilumina de forma continua,
y es imposible realizar las mediciones. En este momento hay que cambiar las baterías.
Si la batería no es reemplazada, después de cinco minutos se apagará automáticamente
el comprobador.
7 Cambio de la batería
Desconectar los cables de medición de la red eléctrica.
Quitar el protector de la carcasa.
Quitar la parte trasera e inferior de la carcasa, y luego sacarla.
Retirar la batería del comprobador, y desconectarla.
Conectar la batería nueva, atornillar la tapa trasera y poner el protector de la carcasa.
8 Limpieza y mantenimiento
NOTA!
Use únicamente el método de conservación indicado por el fabricante en este manual.
El comprobador puede ser limpiado con una trapo suave, humedecido con detergentes
habituales.
No utilice disolventes o productos de limpieza que puedan rayar la carcasa (polvos, pastas, etc.).
El sistema electrónico del probador no requiere mantenimiento.
9 Almacenamiento
Durante el almacenamiento del comprobador hay que observar las siguientes instrucciones:
asegurarse de que el comprobador está seco,
para un almacenamiento prolongado debe quitarse la batería.
10 Desmontaje y utilización
Los residuos de aparatos eléctricos y electrónicos deben ser recogidos por separado; no deben
depositarte con otro tipo de residuos.
El dispositivo electrónico debe ser llevado a un punto de recogida de este tipo de equipos,
conforme a la Ley de residuos de este tipo.
Antes de llevarlo al punto de recogida no debe de desarmarse ninguna parte del equipo.
Observe la normativa vigente en cuanto a la eliminación de los envases, baterías usadas, etc.
TKF-13 MANUAL DE USO
18
11 Datos técnicos
a) tipo de aislamiento según la norma EN 61010-1 ......................................................................doble
b) categoría de seguridad según EN 61010-1 ......................................................................... III 600 V
c) grado de protección de la carcasa según EN 60529 ................................................................ IP42
d) rango de frecuencia .......................................................................................................... 2 ÷ 70 Hz
e) rango de tension nominales entre fases ................................................................ 127 ÷ 690 V AC
f) rango de tensión, entre fases, de trabajo .............................................................. 120 ÷ 760 V AC
g) rango de tensiones SEM de motores .......................................................................... 1 ÷ 760 V AC
h) corriente de medición (por fase) ......................................................................................... <3,5 mA
i) temperatura de trabajo ................................................................................................... -10 ÷ 45ºC
j) temperatura de almacenamiento .................................................................................... -20 ÷ 60ºC
k) tiempo de parpadeo del diodo de batería ............................................................................... ca. 1 s
l) apagado automático .............................................................................................. aprox. 5 minutos
m) alimentación ........................................................................................ batería alcalina 6LR61 (9 V)
n) dimensiones ....................................................................................................... 130 x 72 x 31 mm
o) peso ............................................................................................................................. aprox. 150 g
El dispositivo no tiene el carácter de un patrón, por lo tanto, no está sujeto a
calibración. La forma adecuada de control para este tipo de instrumento es la
verificación.
12 Fabricante
El fabricante del dispositivo que presta el servicio de garantía y postgarantía es:
SONEL S.A.
Wokulskiego 11
58-100 Świdnica
Polonia
tel. +48 74 884 10 53 (Servicio al cliente)
e-mail: customer[email protected]m
internet: www.sonel.com
¡ATENCIÓN!
Para el servicio de reparaciones sólo está autorizado el fabricante.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40

Sonel TKF-13 Manuale utente

Categoria
Misurazione
Tipo
Manuale utente