Munters WM54 Drive Retrofit Kit Manuale del proprietario

Tipo
Manuale del proprietario
1© Munters Corporation, September 2020
QM1099r0
Instruction Manual
Munters Drive
WM54 Retrofi t Kit
Models: RF-WM5421-xx • RF-WM5423-xx • RF-WM5443-xx
Munters Drive*
WM54
Retrofi t Kit
*Patents Pending
© Munters Corporation, September 2020
2
QM1099r0
Munters Drive WM54 Retrofit Kit
Instructions for Use and Maintenance
Thank You:
Thank you for purchasing a Munters Drive WM54 Retrofit Kit. Munters equipment is designed to be the highest
performing, highest quality equipment you can buy. With the proper installation and maintenance it will provide
many years of service.
Please Note:
To achieve maximum performance and insure long life from your Munters product it is essential that it be installed
and maintained properly. Please read all instructions carefully before beginning installation.
Warranty:
For Warranty claims information see the “Warranty Claims and Return Policy” form QM1021 available from the
Munters Corporation office at 1-800-227-2376 or by e-mail at [email protected].
Conditions and Limitations:
• Products and Systems involved in a warranty claim under the “Warranty Claims and Return Policy” shall have
been properly installed, maintained and operated under competent supervision, according to the instructions
provided by Munters Corporation.
Malfunction or failure resulting from misuse, abuse, negligence, alteration, accident or lack of proper installation
or maintenance shall not be considered a defect under the Warranty.
3© Munters Corporation, September 2020
QM1099r0
Index
Chapters Page
1. Unpacking the Equipment 4
1.1 Parts List 4
2. Installation Instructions 5
3. Electrical Wiring 11
3.1 Recommended Wire Routing 11
3.2 Electrical Wiring 13
3.2 Recommended Wiring 13
4. Operation and Maintenance 19
4.1 Operation 19
4.2 Maintenance 19
5. Troubleshooting 20
6. Exploded View and Parts List 21
© Munters Corporation, September 2020
4
QM1099r0
1.1 Parts List
Each Munters Drive Retrofit kit includes:
1 Strut Brace, WM54DK/P, PWDCTD
1 – Munters Drive Motor
1 – Munters Drive Controller
1
Hardware package as follows:
Unpacking the Equipment
1.
HP1393 – Hardware Package
ID Qty. Cat. No. Description
[A] 2 KN1850 M10-1.5 x 10mm Hex Nut, ZP
[B] 2 KW3509 M10, Splitlock Washer, ZP
[C] 2 KW3016
7
16” Type-A Wide Flat Washer, ZP
[D] 4 KS1019
1
4”-20 x 1” Hex Head Bolt, SS
[E] 4 KW3002
1
4” Type-A Narrow Flat Washer, SS
[F] 4 KN0702
1
4”-20 Serrated Flange Hex Nut, SS
[G] 4 KS2258 #10-16 x
5
8” HXWSR TEK Screw, SS
[H] 4 KX1018
3
8” Dia. X
1
2W. Wire Clamp, BLK NY
[J] 1 KX1157 1” Dia. Hole Plug, Black Rubber
[K] 2 KS1007
5
16”-18 x 1.25” Hex Head Bolt, SS
[L] 2 KN0704
5
16”-18 Serrated Flange Hex Nut, SS
[M] 2 KW4908 M8 x 32mm Flat Washer, ZP
[A]
[B]
[C]
[D]
[E]
[F]
[G]
[H]
[J]
[K]
[L]
[M]
5© Munters Corporation, September 2020
QM1099r0
Installation Instructions
2.
2.1 Installation
Figure 1
Figure 2
Step 2
Remove Bolts, Washers and Nuts holding the propeller to the hub and carefully set propeller into the
cone to be reused. See Figure 2.
Step 1
Disconnect power from fan before continuing. Remove the rear guard from the back of the fan and set
safely aside to be reinstalled later. See Figure 1.
Bolt, Washer and Nut
to be removed
© Munters Corporation, September 2020
6
QM1099r0
Installation InstructionsChapter 2
Step 3
Disconnect the electrical power leads from the motor. Remove belt from fan. Remove lag screw from
stiffener bracket. Remove the (3) bolts and (6) nuts holding the motor base and tensioner bracket to strut
and remove motor with base and tensioner from fan. See Figure 3.
Figure 3
Remove Bolt, Nuts and Washer
Tensioner Bracket
Motor Base
Remove Lag Screw
Step 4
Remove Screw and Cap covering the Nut on the back of the Hub Shaft. Remove Nut holding Hub to
Strut, then remove Hub/Sheave assembly from fan. See Figure 4.
Figure 4
Remove Screw and Cap
Remove Nut
Remove Hub with Sheave
7© Munters Corporation, September 2020
QM1099r0
Figure 6
Step 5
Locate box and make sure it is facing up and open the box. Remove the top section of the foam packaging
to reveal the Munters Drive Motor and Controller. If the cable from the Controller is connected to the motor
then disconnect the cable with the quick connector from the motor. See Figure 5.
Figure 5
Motor
Nut [A]
Installation InstructionsChapter 2
(top) Foam Packaging
Controller
Munters Drive
Step 6
The Motor in the foam packaging has pre-installed bolts sticking up. Carefully remove the Motor from the
foam packaging and from the outside of the fan slide the motor onto the strut so the bolts go through the 2
small holes at the center of the strut and fasten in place using (2) Washers [C], Splitlock Washers [B] and
Nuts [A]. Then install (1) Hole Plug [J] in the large center hole of the strut. See Figure 6.
Splitlock Washer [B]
Washer [C]
Hole Plug [J]
© Munters Corporation, September 2020
8
QM1099r0
Installation InstructionsChapter 2
Figure 8
Receptacle
Nut [F]
Quick Connect Connector
Step 8
Find Strut Brace and remove Controller from foam packaging. Plug the Quick Connect Connector into Motor
and position Controller and Strut Brace over Strut, with bottom of box toward bottom of fan. Secure Controller
and Strut Brace to Motor using (4) Bolts [D], Washers [E] and Nuts [F]. See Figure 8.
Strut Brace
Washer [E]
Bolt [D]
Controller
Figure 7
Step 7
Remove (4) Nuts from face of the Munters Drive Motor. Position Propeller onto bolts on Munters Drive Motor
and secure with (4) Nuts just removed. Tighten the Nuts to 200 in-lbs. of torque. See Figure 7.
Propeller
Nuts
Bolts on Motor
Munters Drive Motor
9© Munters Corporation, September 2020
QM1099r0
Step 9
Where the bottom of the Strut Brace meets the Orifice Panel, use the 2 holes in the Strut Brace as
a guide and drill (2) ⁄” holes through the fiberglass Orifice Panel. Secure Strut Brace to Orifice
Panel using (2) Bolts [K], Washers [M] and Nuts [L]. See Figure 9.
Figure 9
Figure 10A
Step 10A
Cut a section of the Inlet Guard out to fit over the motor. When cutting the guard wires make sure
to cut them as close to the other wires as possible. Save cut-out section to cover the existing hole.
See Figure 10A.
Bolts [K]
Nuts [L]
Strut Brace
Washers [M]
Installation InstructionsChapter 2
Holes in Strut Brace
© Munters Corporation, September 2020
10
QM1099r0
Installation InstructionsChapter 2
Step 10B
Position new guard cut-out over the old hole in the guard where the old motor protruded through and fasten
it in place using Zip-Ties (not provided). Place guard against framing and fasten guard in place using
existing Shutter Clips or J-Nails. See Figure 10B.
Figure 10B
New Guard
Cut-Out
Existing Guard
Existing Guard
11© Munters Corporation, September 2020
QM1099r0
3.1 Recommended Wire Routing:
The Munters Drive Kit comes with a coil of electrical cable that is pre-wired to controller. Find the end of the
cable and route the cable up the strut and out of the fan. Create a drip loop in the bottom of the cable and
then fasten it to the strut using (4) Wire Clamps [H] and TEK Screws [G]. Attach the new cable to the power
supply for the fan. See Figure 11A and 11B. Continue on next page
Figure 11A
Electrical Cable
Drip Loop
Electrical Wiring
3.
WARNING: Fan is designed to be operated with shutter in place. Do not apply power to fan without
shutter being installed.
Wire clamps [H]
& TEK screws [G]
© Munters Corporation, September 2020
12
QM1099r0
Electrical WiringChapter 3
KEY:
L1=Line 1
L2=Line 2
L3=Line 3
H=Hot
N=Neutral
G=Ground
All wiring should be installed in accordance with National, State, and Local electrical
codes. Fans used to ventilate livestock buildings or other rooms where continuous air
movement is essential should be connected to individual electrical circuits, with a minimum
of two circuits per room. For electrical connection requirements, refer to diagram on motor
nameplate and to information enclosed with the environmental control to be used.
Single Phase and Three Phase Munters Drives: Power supply for fans to have Circuit
Breaker or Fuse Protection. The installer must refer to NEC and local codes to ensure safety
and compliance. See Figure 11B and 11C.
If recommended lightning protection was purchased, wire it to the fan power supply as shown and secure the
lightning protection unit near the disconnect or the bus panel. See Figure 11B and 11C.
NOTE: A safety cut-off switch should be located adjacent to each fan.
T1
T2
T3
G
Three Phase
Power Out to Fan Motor
Three Phase
Power Supply for Fan
L1
L2
L3
G
Safety
Cut-Off Switch
Recommended Lightning Protection
FC2023-UL, 230V, 1 Phase
230 VAC
Power Supply for Fan
L1
L2
G
T1
T2
G
230 VAC
Power Out to Fan
Figure 11C
Three Phase
Figure 11B
Single Phase
Safety
Cut-Off Switch
Recommended Lightning Protection
FC2026-UL, 230V, 3 Phase
FC2029-UL, 460V, 3 Phase
3.2 Electrical Wiring
WARNING
!
Disconnect Power
Before Servicing
13© Munters Corporation, September 2020
QM1099r0
Electrical WiringChapter 3
3.3 Recommended Wiring
Figure 12A
Default Operation Full Speed
The Munters Drive fan ships configured for simple ON/OFF operation. When electrical power is applied to
the main cable and the ‘RUN’ Switch is in the ‘ON’ Position, the fan will start and run at full speed.
See Figure 12A.
***WARNING***
The Blue Box electrical enclosure must not be
removed from mounting bracket. Removing
Blue Box from the mounting bracket will void the
warranty. Any water or other damage to the
controller will not be covered if the Blue Box is
removed.
***NOTE***
All Low Voltage wire must be shielded
cable. i.e. Belden 8770 or equivalent.
© Munters Corporation, September 2020
14
QM1099r0
Electrical WiringChapter 3
When making connections to Munters Drive Box, be sure to use the supplied watertight fittings with only
1 cable per fitting. If watertight fittings are not used or if 2 cables or more are in 1 watertight fitting,
equipment failure from water damage will not be covered under warranty. If 2 or more cables are used in
1 watertight fitting, they must be sealed on both sides of Munters Drive Box wall to prevent water infiltration.
If you are going to run the Munters Drive with a signal from a control, carefully remove 6 screws and the
cover and save to reinstall later. Carefully punch the knock-out from the bottom of the Munters Drive Box and
install the Watertight connector as shown. See Figure 12B and 12C.
Figure 12B
Figure 12C
15© Munters Corporation, September 2020
QM1099r0
Electrical WiringChapter 3
Figure 12D
On/Off Remotely
To operate the Munters Drive On/Off with a control, Slide the ‘RUN’ switch, located on the circuit board in
the Munters Drive Box, to the ‘OFF’ position. Now wire an ‘ON’ command from the ‘COMMON’ terminal
to the input relay in the control and from the output of the control relay to the ‘RUN’ terminal in the Munters
Drive Box. See Figure 12A and 12D.
***WARNING***
The Blue Box electrical enclosure must not be
removed from mounting bracket. Removing
Blue Box from the mounting bracket will void the
warranty. Any water or other damage to the
controller will not be covered if the Blue Box is
removed.
***NOTE***
All Low Voltage wire must be shielded
cable. i.e. Belden 8770 or equivalent.
© Munters Corporation, September 2020
16
QM1099r0
Electrical WiringChapter 3
To operate the Munters Drive Off/Low/High with a control, slide the ‘RUN’ switch, located on the circuit
board in the Munters Drive Box, to the ‘OFF’ position. Now wire an ‘ON’ command from the ‘COMMON’
terminal to the input relay in the control and from the output of the relay to the ‘RUN’ terminal in the Munters
Drive Box. Then connect the output of the control relay for ‘LOW’ to the ‘REDUCED FLOW’ terminal in the
Munters Drive Box. See Figure 12E.
Figure 12E
Off/Low/High Remotely
***WARNING***
The Blue Box electrical enclosure must not be
removed from mounting bracket. Removing
Blue Box from the mounting bracket will void the
warranty. Any water or other damage to the
controller will not be covered if the Blue Box is
removed.
***NOTE***
All Low Voltage wire must be shielded
cable. i.e. Belden 8770 or equivalent.
17© Munters Corporation, September 2020
QM1099r0
Electrical WiringChapter 3
Figure 12F
Variable Speed Operation
To Operate the Munters Drive variable with a 10-0V Signal, slide the ‘RUN’ switch, located on the circuit
board in the Munters Drive Box, to the ‘ON’ position. Connect wires from the ‘0-10V IN’ and ‘0-10V
COMMON’ terminals in the Munters Drive Box to the 10-0V output in the control. See Figure 12F.
***WARNING***
The Blue Box electrical enclosure must not be
removed from mounting bracket. Removing
Blue Box from the mounting bracket will void the
warranty. Any water or other damage to the
controller will not be covered if the Blue Box is
removed.
***NOTE***
All Low Voltage wire must be shielded
cable. i.e. Belden 8770 or equivalent.
© Munters Corporation, September 2020
18
QM1099r0
Electrical WiringChapter 3
To operate the Munters Drive Off/Variable with a 10-0V Signal, slide the ‘RUN’ switch, located on the circuit
board in the Munters Drive Box, to the ‘OFF’ position. Now wire an ‘ON’ command from the ‘COMMON’
terminal to the input relay in the control and from the output of the control relay to the ‘RUN’ terminal in
the Munters Drive Box. Also, connect wires from the ‘0-10V IN’ and ‘0-10V COMMON’ terminals in the
Munters Drive Box to the 10-0V output in the control. See Figure 12G.
Figure 12G
On/Off with Variable Speed Operation
WARNING: Fan is designed to be operated with shutter in place. Do not apply power to fan without
shutter being installed.
19© Munters Corporation, September 2020
QM1099r0
1) INITIAL START-UP: With electrical power off, verify that the fan propeller
turns freely and that all fasteners are secure. Turn on electrical power and
confirm that the fan operates smoothly.
2) ADJUSTMENTS: Set the fan control to the temperature shown on your
Aerotech ventilation system drawing, or to a value which will provide the
desired environmental conditions.
4.1 Operation
Operation and Maintenance
4.
4.2 Maintenance
The following inspection and cleaning procedures should be performed monthly:
1) INSPECT PROPELLER: Check that propeller is secure on drive hub and that
there are no signs of damage. The blades are of a self-cleaning design and should
not require maintenance.
2) CLEAN regularly for best results:
FAN MOTOR: Remove any dust accumulation from motor using a brush or
cloth. (DO NOT use a pressure washer). A clean motor will run cooler and last longer. At the
same time, verify that the motor is secure in its mount.
DAMPER: Carefully clean dust from damper door and frame so that damper door opens and
closes freely. A brush or cloth should be used.
GUARD: Clean any dust or feathers from fan guards using a brush. Dirty guards can reduce
airflow.
3) CHECK FASTENERS: For safety, all fasteners should be inspected 1 month after initial operation
and yearly thereafter. Tighten any loose connections.
4) INSPECT FAN CONTROL: With power disconnected, inspect all electrical connections. Wiring
should be secure and in good condition. Remove any dust build-up from control case and sensor
using a soft brush or cloth. NEVER CLEAN ELECTRICAL EQUIPMENT WITH A PRESSURE
WASHER!
WARNING
!
Disconnect Power
Before Servicing
WARNING
!
Moving Parts, Disconnect
Power Before Servicing.
WARNING
!
Do Not Power Wash
Electrical Devices.
© Munters Corporation, September 2020
20
QM1099r0
Troubleshooting
5.
SYMPTOM POSSIBLE CAUSES CORRECTIVE ACTION
Fan Not Operating Fan control set above room
temperature
Blown Fuse or open circuit breaker
Propeller blade contacting fan
housing
Fan control defective (i.e.
environmental control, etc.)
Set to a lower temperature
Replace fuse or reset breaker
Realign motor in fan housing
Repair or replace control
Fan Does Not Start
Caution: There is a 10 second
delay for the fan to start when
an 'On' command is present.
Munters Drive motor/controller
issue
1. Verify AC voltage is present at fan.
2. Turn AC power off to fan for 1 minute
3. Verify Prop turns freely
a. If not contact Munters Product Support
b. If it turns freely go to next step
4. Turn AC power back on to fan
a. If starts up and runs, fan OK
•Periodically observe fan to verify it is still running
•If it continues to run, fan is OK
•If fan stops, look through clear window in drive
cover to check what drive display reads.
Contact Munters Product Support
b. If fan tries to start but stops, look through clear
window in drive cover to check what drive display
reads. Contact Munters Product Support
c. If fan doesn't try to start, verify 'On' command
signal is present at circuit board. Also, slide the
switch on the circuit board to the 'On' position.
Fan Operating - Insuffi cient
Airfl ow
Excessive Noise
Excessive Vibration
Shutter or Damper door jammed
Guard dirty/clogged
10-0V signal set incorrectly
Propeller blade contacting fan
housing
Motor loose on mount
Propeller damaged
Clean shutter or damper door
Clean guard
Check and adjust 10-0V signal
Sand fan housing to remove high spot
Tighten fasteners
Replace propeller
5.1 Troubleshooting
WARNING
!
Disconnect Power
Before Servicing
WARNING
!
Moving Parts, Disconnect
Power Before Servicing.
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22

Munters WM54 Drive Retrofit Kit Manuale del proprietario

Tipo
Manuale del proprietario