Photocell 1 and Photocell 2 Connections
Note: If the photocells are not connected, it is not necessary put a jumper between the clamps
(6 and 7 and/ou 6 and 8 of the CN1 terminal)
24VA = AUX 24V (Accessories) 800 mA max COM = 0V PH1 = Photocell contact 1
PH2 = Photocell contact 2
Note: For the autotest in the fototest menu select the photocell or the photocells on which you want
to perform it. Auto-test is possible only when the transmitter of the photocell is powered on 24V~.
The default setting of the photocell 1 is FOTO CLOSE and the one of the photocell 2 is FOTO OPEN.
The photocell 2 can also be set as TIMER (see TIMER function).
TIMER
Options AUX 24V 800 mA max can be set with on-board
Display or with Jolly device.
It is possible to chose when having tension on the AUX output.
The options are: always, only during opening, only during
cycle, only before opening or only during pause or for the
management of the positive or negative electrobrake.
N.B: For the autotest connect
the transmitters to the
contacts 20 and 21, if you do
not want the autotest connect
the transmitters to the
contacts 19 and 20.
67411385
START - STOP - PEDESTRIAN START - ANTENNA -
PHOTOCELL
PEDESTRIAN START (N.O.) The pedestrian start can be connected
between the conectors 2 and 4 of the CN1 terminal .
This input allows a partial opening, the opening space can be set through
the on-board display or through the JOLLY device.
Note1: The contact for partial opening is a N.O. Contact (Normally open).
Holding START starts the TIMER function, releasing the pedestrian start,
the operator repeats the pause and then performs the closing. In the case
of triggering a safety device the timer will automatically reset after 6
seconds.
Note2:In 2 BUTTONS logic it is necessary to keep pressed the Start Ped.
to re-close the automation.
Note3: In deadman logic this button executes the re-closing if you keep it
pressed.
Note4: When closed during pause, the gate will reclose only after this
input has been reopened.
TIMER activation: This input can be transformed into TIMER (See
TIMER).
START (N.O.) The
An impulse given to this contact opens and closes the automation depending on the selected logic, it can be given by a keyswitch, a keypad, etc.
To connect the other devices refer to the related instructions leaflets. (ie. loop detectors and proximity switches).
Note1: In DEADMAN logic keep pressed the Start for the opening of the automation.
Note2:
START is connected between connector 2 and 3 of the CN 1 terminal.
In the case of triggering a safety device
the timer will automatically reset after 6 seconds.
Holding START starts the TIMER function, releasing the start, the operator repeats the pause and then performs the closing.
In 2 BUTTONS logic this button performs the opening.
STOP (N.C.) The STOP is connected between the clamps 2 and 5 of the CN1 terminal .
When pressing this button the motor immediately stops in any condition/position. To re-start the movement give a start command.
After a stop the motor always re-starts in closing.
Can be activated through the on-board display or through the Jolly programmer. In both cases it’s a N.O. contact which provoques the
opening of the automation keeping it open as long as it is activated. When it’s released, after having paused for the set pausing time the
gate recloses. The TIMER can be activated on the inputs FOTO2, PEDESTRIAN START or keeping busy the START input.
Note1: When activated on the pedestrian entry, the pedestrian will be OFF also on the radio transmitter.
Note2: In the event of an intervention of a security device during the timer (Stop, amperometric, Edge), a start impulse restors the
movement.
Note3: In case of no power supply with open gate and active Timer the control unit will restore its function, otherwise if during restoring of
the power supply the TIMER is not activated it will be necessary to give a start impulse for the reclosing.
10 11 12 13
1 2 3 4 5 6 7 8 9
-
3
6
5
6
4
START
PEDESTRIAN
START
STOP
C
CN2
RX1
RX2
TX1
TX2
6
7
6
8
14 15 16 17 18 19 20 21 22 23
14 15 16 17 18 19 20 21 22 23
20
21
19
20
19
20
20
21
CN2
CN1
OPTIONS ON FOTO1 and FOTO2 adjustable on on- board display or with JOLLY
terminal.
FOTO CLOSE activation ((losing): if occupied, reverses the movement in closing,
during pause it prevent the closing.
Activation repeat pause (pavse RELOAD): If occupied, during pause it recharges the
timer of pause. In closing it reverses the movement.
FOTO OPEN activation (oPEning): If activated the photocell blocks the movement as
long as it’s busy, when released the opening continues.
FOTO PARK activation (stop and (lose): in opening it is not active; in pause are
activated it commands the closing when released, otherwise it’s not active; in closing it
stops the movement as long as it is busy, when released the closing continues.
FOTO STOP activation (STOP): When activated before the opening the photocell
blocks the automation as long as it is busy, during the opening it will be ignored. In
closing the intervention of the photocell causes the reopening.
Activation PHOTO CLOSE IMMEDIATELY ((lose): The photocell stops the gate as
long as it is occupied in both opening and closing, when released it gives a closing
command (Closing one second after release of the photocell ).
Activation delay pause TI E: If the photocell is occupied during opening, pause or
closing, the gate reopens completely and closes without observing the pause time.