Select type of logic for START input with DIP 4
This type of logic is to be selected after the Learning-Phase
ü DIP4 in OFF : The input-Start Open, assumes the function of
the Start. So button connected to this input will function either
by command that opens and closes.
ü DIP4 in ON : The entrance Start-Open, assumes the function
of command opens both impulsive or dead man. So, the button
connected to this input, it will work just as command opens. In
this case, will have to be used the Command Closes, (Close)
for the reclosing.
ON
1 2 3 4
SW1
ON
OFF
ü Place the automation in closed position
ü Hold the P3 until the display shows
ü Press pedestrian start: automation will start in opening
ü Press pedestrian start when you want the automation to stop.
ü Wait until the desired wait time and press pedestrian start.
ü The automation starts closing.
ü Arrived on the opening limit switch, automation will stop.
ü Learning partial working time (Pedestrian)
Function 03 - Changing pause time
Hold the P3 until the display shows e release P3
ü Press repeatedly P2 until appears on the display.
ü Press P3 and on the display .
appears = 4 seconds of pause or the one set in
learning.
ü Press the button P1 to increase and P2 to decrease the time in seconds
ü Press P3 for confirmation
If you want to quit the programming mode follow the procedure for ESC:
Press P2 (Forward) or P1 (Backward) until you see
Confirm pressing P3.
Function 04 – Max torque adjustment.
ü Hold the P3 until the display shows e release P3
ü Press repeatedly P2 until appears on the display.
ü Press P3, the display show . = the percentage of the maximum torque set.
ü Press the button P1 to increase and P2 to decrease the value.
ü Press P3 for confirmation
If you want to quit the programming mode follow the procedure for ESC:
Press P2 (Forward) or P1 (Backward) until you see
Confirm pressing P3.
www.quikoitaly.com