SICK Flexi Gateway GPNT1 Expansion module - gateway Istruzioni per l'uso

Tipo
Istruzioni per l'uso
O P E R A T I N G I N S T R U C T I O N S
Flexi Gateway GPNT1
Expansion module - gateway
Described product
F
lexi Gateway GPNT1
Manufacturer
SICK AG
Erwin-Sick-Str. 1
79183 Waldkirch
Germany
Legal information
T
his work is protected by copyright. Any rights derived from the copyright shall be
reserved for SICK AG. Reproduction of this document or parts of this document is
only permissible within the limits of the legal determination of Copyright Law. Any modi‐
fication, abridgment or translation of this document is prohibited without the express
written permission of SICK AG.
The trademarks stated in this document are the property of their respective owner.
© SICK AG. All rights reserved.
Original document
T
his document is an original document of SICK AG.
2
O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1 8024581/2020-11-10 | SICK
Subject to change without notice
Contents
1 About this document........................................................................ 5
1.1 Purpose of this document........................................................................ 5
1.2 Scope......................................................................................................... 5
1.3 Target groups and structure of these operating instructions................ 5
1.4 Further information................................................................................... 6
1.5 Symbols and document conventions...................................................... 6
2 Safety information............................................................................ 8
2.1 General safety notes................................................................................ 8
2.2 Intended use............................................................................................. 8
2.3 Improper use............................................................................................. 8
2.4 Requirements for the qualification of personnel.................................... 8
3 Product description........................................................................... 10
3.1 Configuration of the safety controller...................................................... 10
3.2 Overview of the module............................................................................ 11
3.3 Configuration and function...................................................................... 11
3.4 Status indicators....................................................................................... 12
4 Project planning................................................................................ 13
4.1 Design........................................................................................................ 13
4.2 Integration into the controller network.................................................... 13
4.2.1 Network topology..................................................................... 13
4.2.2 Integration via the fieldbus interface..................................... 14
4.2.3 Integration via the TCP/IP socket interface........................... 14
5 Mounting............................................................................................. 16
5.1 Safety......................................................................................................... 16
5.2 Mounting procedure................................................................................. 16
5.3 Module exchange...................................................................................... 16
6 Electrical installation........................................................................ 17
6.1 Safety......................................................................................................... 17
6.2 Device connection.................................................................................... 17
7 Configuration..................................................................................... 18
7.1 Offline, online and security configuration............................................... 18
7.2 Configuring the network interfaces......................................................... 19
7.2.1 Configuring the higher-level controller.................................... 19
7.2.2 Addressing................................................................................ 20
7.2.3 Deactivating alarms................................................................. 20
7.2.4 Configuring the TCP/IP socket interfaces.............................. 20
7.2.5 Configuring the output data (routing to CPU)......................... 21
7.2.6 Configuring the input data (routing to network)..................... 22
CONTENTS
8024581/2020-11-10 | SICK O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1
3
Subject to change without notice
8 Commissioning.................................................................................. 24
8.1 Check during commissioning and modifications.................................... 24
9 Operation............................................................................................ 25
9.1 Operation of the display........................................................................... 25
9.2 Display menu............................................................................................ 25
9.3 Regular thorough check........................................................................... 25
10 Maintenance...................................................................................... 26
10.1 Regular thorough check........................................................................... 26
11 Troubleshooting................................................................................. 27
11.1 Status indicators....................................................................................... 27
11.2 Possible faults........................................................................................... 28
12 Decommissioning............................................................................. 30
12.1 Disposal..................................................................................................... 30
13 Technical data.................................................................................... 31
13.1 Data sheet................................................................................................. 31
13.2 Data exchange in the network................................................................. 32
13.2.1 PROFINET................................................................................. 32
13.2.2 TCP/IP socket interface........................................................... 38
13.3 Dimensional drawings.............................................................................. 46
14 Ordering information........................................................................ 48
14.1 Scope of delivery....................................................................................... 48
14.2 Ordering information for main module.................................................... 48
14.3 Ordering information for expansion module........................................... 48
14.4 Ordering information for accessories...................................................... 48
15 Annex.................................................................................................. 50
15.1 Compliance with EU directives................................................................. 50
16 List of figures..................................................................................... 51
17 List of tables....................................................................................... 52
CONTENTS
4
O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1 8024581/2020-11-10 | SICK
Subject to change without notice
1 About this document
1.1 Purpose of this document
These operating instructions contain the information required during the life cycle of the
s
afety controller.
Operating instructions of the safety controller must be made available to all people who
work with the device.
1.2 Scope
These operating instructions apply to the Flexi Compact safety controller.
T
his document is included with the following SICK part numbers (this document in all
available language versions):
8024567
Furthermore, the following documents contain information about the safety controller:
T
able 1: Available documents
Document Title Part number
Operating instructions FLX3-XTDI1 expansion module
f
or safety controllers
8024571
Operating instructions FLX3-XTDO1 expansion mod‐
ule for safety controllers
8024570
Operating instructions FLX0-GPNT1 expansion mod‐
ule f
or safety controllers
8024567
Operating instructions FLX0-GETC1 expansion mod‐
ule for safety controllers
8024566
Operating instructions Flexi Loop Safe Series Con‐
nection Hardware
8015834
Operating instructions Flexi Loop in the Safety
D
esigner Software
8018174
Competence brochure Guide for Safe Machinery 8008007
1.3 Target groups and structure of these operating instructions
These operating instructions are intended for the following target groups: project devel‐
oper
s (planners, developers, designers), installers, electricians, safety experts (such as
CE authorized representatives, compliance officers, people who test and approve the
application), operators, and maintenance personnel.
These operating instructions are organized by the life phases of the device: project
planning, mounting, electrical installation, commissioning, operation and maintenance.
The table below shows the target groups and how – for many applications – these are
typically divided up between the manufacturer and the entity operating the machine in
which the device is to be integrated:
ABOUT THIS DOCUMENT 1
8024581/2020-11-10 | SICK O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1
5
Subject to change without notice
Area of responsibility Target group Specific chapters of these operating instruc‐
t
ions
1)
Manufacturer Project developers
(planners, developers,
designers)
Project planning, page 13
Technical data, page 31
Installers Mounting, pa
ge 16
Electricians Electrical installation, page 17
Safety experts Project planning, pa
ge 13
Commissioning, page 24
Technical data, page 31
Operating entity Operators Troubleshooting, pa
ge 27
Maintenance staff Troubleshooting, page 27
Ordering information, page 48
1)
Chapters not listed here are intended for all target groups. All target groups must follow all of the safety
and warning instructions in all chapters of the operating instructions!
In other applications, the operating organization is also the manufacturer of the equip‐
ment w
ith the corresponding allocation of the target groups.
1.4 Further information
www.sick.com
T
he following information is available via the Internet:
This document in other languages
Data sheets and application examples
CAD files and dimensional drawings
Certificates (such as the EU declaration of conformity)
Guide for Safe Machinery. Six steps to a safe machine
Safety Designer (software for configuring safety solutions made by SICK AG)
1.5 Symbols and document conventions
The following symbols and conventions are used in this document:
Safety notes and other notes
DANGER
Indicates a situation presenting imminent danger, which will lead to death or serious
injuries if not prevented.
WARNING
Indic
ates a situation presenting possible danger, which may lead to death or serious
injuries if not prevented.
CAUTION
Indic
ates a situation presenting possible danger, which may lead to moderate or minor
injuries if not prevented.
NOTICE
Indic
ates a situation presenting possible danger, which may lead to property damage if
not prevented.
1 ABOUT THIS DOCUMENT
6
O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1 8024581/2020-11-10 | SICK
Subject to change without notice
NOTE
Indic
ates useful tips and recommendations.
Instructions to action
b
T
he arrow denotes instructions to action.
1. The sequence of instructions for action is numbered.
2. Follow the order in which the numbered instructions are given.
The check mark denotes the result of an instruction.
ABOUT THIS DOCUMENT 1
8024581/2020-11-10 | SICK O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1
7
Subject to change without notice
2 Safety information
2.1 General safety notes
This chapter contains general safety information about the safety controller.
F
urther safety information is provided in the respective chapters to cover the specific
situations in which the product may be used.
DANGER
If t
he device is not integrated in the way intended by the manufacturer, the protective
function of the device can be impaired. The dangerous state may be ended too late.
b
Plan the integration of the safety component in accordance with the machine
requirements, see "Project planning", page 13.
2.2 Intended use
The Flexi Compact safety controller is a freely configurable control for safety applica‐
t
ions. Sensors and switching elements (e.g. light curtains, laser scanners, switches,
sensors, encoders, emergency stop pushbuttons) are connected to the safety controller
and are linked logically. The corresponding actuators of the machines or systems can
be switched off safely via the switching outputs of the safety controller.
Incorrect use, improper modification or manipulation of the module will invalidate any
warranty from SICK; in addition, any responsibility and liability of SICK AG for damage
and secondary damage caused by this is excluded.
The safety controller system is only suitable for use in industrial environments.
2.3 Improper use
Among others, the safety controller is not suitable for the following applications:
Out
doors
Underwater
In explosion-hazardous areas
In residential areas
2.4 Requirements for the qualification of personnel
The protective device must be configured, installed, connected, commissioned, and
ser
viced by qualified safety personnel only.
Project planning
For project planning, a person is considered competent when he/she has expertise and
experience in the selection and use of protective devices on machines and is familiar
with the relevant technical rules and national work safety regulations.
Mechanical mounting, electrical installation, and commissioning
F
or the task, a person is considered qualified when he/she has the expertise and
experience in the relevant field and is sufficiently familiar with the application of the
protective device on the machine to be able to assess whether it is in an operationally
safe state.
2 S
AFETY INFORMATION
8
O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1 8024581/2020-11-10 | SICK
Subject to change without notice
Operation and maintenance
F
or operation and maintenance, a person is considered competent when he/she has
the expertise and experience in the relevant field and is sufficiently familiar with the
application of the protective device on the machine and has been instructed by the
machine operator in its operation.
SAFETY INFORMATION 2
8024581/2020-11-10 | SICK O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1
9
Subject to change without notice
3 Product description
3.1 Configuration of the safety controller
Configuration of the safety controller
A s
afety controller comprises the following components:
A main module
Up to 12 optional expansion modules (excluding maximum 1 gateway)
I3
I5
Q1
Q7
I4
I6
Q2
Q8
A2
I7
Q3
Q5
A1
I8
Q4
Q6
I2
PWR
I1
I3
I5
Q1
Q7
I4
I6
Q2
Q8
A2
I7
Q3
Q5
A1
I8
Q4
Q6
I2
PWR
I1
I3
I5
Q1
Q7
I4
I6
Q2
Q8
A2
I7
Q3
Q5
A1
I8
Q4
Q6
I2
PWR
I1
I3
I5
Q1
Q7
I4
I6
Q2
Q8
A2
I7
Q3
Q5
A1
I8
Q4
Q6
I2
PWR
I1
I3
I5
Q1
Q7
I4
I6
Q2
Q8
A2
I7
Q3
Q5
A1
I8
Q4
Q6
I2
PWR
I1
I3
I5
Q1
Q7
I4
I6
Q2
Q8
A2
I7
Q3
Q5
A1
I8
Q4
Q6
I2
PWR
I1
I3
I5
Q1
Q7
I4
I6
Q2
Q8
A2
I7
Q3
Q5
A1
I8
Q4
Q6
I2
PWR
I1
I3
I5
Q1
Q7
I4
I6
Q2
Q8
A2
I7
Q3
Q5
A1
I8
Q4
Q6
I2
PWR
I1
I3
I5
Q1
Q7
I4
I6
Q2
Q8
A2
I7
Q3
Q5
A1
I8
Q4
Q6
I2
PWR
I1
I3
I5
Q1
Q7
I4
I6
Q2
Q8
A2
I7
Q3
Q5
A1
I8
Q4
Q6
I2
PWR
I1
I3
I5
Q1
Q7
I4
I6
Q2
Q8
A2
I7
Q3
Q5
A1
I8
Q4
Q6
I2
PWR
I1
1
2
3
FLEXIcompact
CV
I1
I3
I7
X1
I2
I4
I8
X
2
X
4
I5
I9
I11
X3
I6
I10
I12
I15
I17
X5
Q3
I16
I18
X6
Q4
A2
I19
X7
Q1
A1
I20
X8
Q2
I14
PWR
I13
Figure 1: Example maximum configuration
1
Main module
2
Expansion module - gateway
3
IO expansion module
Complementary information
The gateway and IO expansion modules can be arranged arbitrarily.
3 PRODUCT DESCRIPTION
10
O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1 8024581/2020-11-10 | SICK
Subject to change without notice
3.2 Overview of the module
1
2
3
4
5
Figure 2: Gateway expansion module
1
Release element of the module
2
Display
3
RJ45 female connector
4
RJ45 female connector
5
Backplane bus
3.3 Configuration and function
Prerequisites
T
he module can only be operated with a main module.
Configuration
Table 2: Interfaces of the module
Description Quantity
RJ45 female connector 2
Function
T
he module enables a safety controller to send data to a network for control and
diagnostic purposes, and to receive data from the network.
The module offers the following functions:
Integration into a PROFINET IO network as a field device
Communication of multiple applications with the safety controller via TCP/IP sock‐
ets
Configuration of the safety controller via TCP/IP
The module is equipped with an integrated switch. The switch enables the module to
be connected to another Ethernet component (e.g., to a computer) without having to
interrupt the connection of the fieldbus network.
PRODUCT DESCRIPTION 3
8024581/2020-11-10 | SICK O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1
11
Subject to change without notice
Complementary information
V
oltage is supplied to the module via the backplane bus. Communication with the
main module of the safety controller also occurs via the backplane bus.
3.4 Status indicators
Status indicators
Figure 3: Status indicators
Status indicator
T
able 3: Status indicator
Labeling Color Function
PWR Green/Red Device status
BF Green PROFINET operational status
P1 … P2 Green/yellow/white Network activity for Ethernet
R
J45 female connector 1 and
female connector 2
Further topics
"Oper
ation", page 25
"Troubleshooting", page 27
3 P
RODUCT DESCRIPTION
12
O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1 8024581/2020-11-10 | SICK
Subject to change without notice
4 Project planning
4.1 Design
Mounting
En
vironment meets the requirements of IP54 or higher, e.g., IP54 control cabinet.
Mounting on a 35 mm × 7.5 mm mounting rail in accordance with IEC 60715.
The mounting rail is connected to the functional earth.
Mounting rail is mounted on a mounting plate.
Mounting plate is connected to functional earth.
Mounting in a vertical orientation (on a horizontal mounting rail).
Take suitable ESD protection measures.
Air circulation
To ensure sufficient air circulation and cooling, sufficient distance must be kept in the
control cabinet above and below the module.
Provide an adequate clearance in front of the module (front side) for the connected
cables.
≥ 30≥ 30
≥ 25
Figure 4: Clearances for adequate air circulation
R
equired distance:
Above and below the module: ≥ 30 mm
In front of the module: ≥ 25 mm
4.2 Integration into the controller network
4.2.1 Network topology
The gateway is suitable for the following network topologies:
S
tar
Line
PROJECT PLANNING 4
8024581/2020-11-10 | SICK O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1
13
Subject to change without notice
Rin
g
Tree
4.2.2 Integration via the fieldbus interface
Prerequisites
T
he generic station description (GSDML file) is installed in the hardware catalog of
the higher-level controller.
Parameters to be configured
Parameter:
Unique device name
If applicable, the IP address of the router with associated subnet mask
You can configure the parameters via the following interfaces:
Safety Designer
Configuration software for the relevant fieldbus network
PROFINET controller
Display on the gateway
Complementary information
Y
ou can find the required device description file and the device symbol for integration
into a higher-level controller in the following locations:
On the Internet on the gateway product page at www.sick.com
In the configuration software program directory on the computer
4.2.3 Integration via the TCP/IP socket interface
Overview
Y
ou can integrate the gateway into a network via TCP/IP sockets in parallel to the
fieldbus.
The gateway supports multiple TCP/IP socket interfaces. This enables multiple applica‐
tions to communicate with the safety controller at the same time.
Table 4: TCP/IP socket interfaces
Number of TCP/IP socket interfaces 4
Number of possible connections per TCP/IP socket 6
Total number of connections 24
Important information
NOTE
R
emote TCP/IP connections with excessive signal propagation times can be unstable.
Signal propagation times > 300 ms may result in the connection being terminated.
b
Take account of signal propagation times in the case of remote TCP/IP connec‐
tions.
b
Use the ping command to check the signal propagation time.
b
If necessary, change the routing.
Client or server
Y
ou configure the module as a client or as a server in Safety Designer.
4 P
ROJECT PLANNING
14
O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1 8024581/2020-11-10 | SICK
Subject to change without notice
W
hen the module is configured as a server, the application reads the input data
from the module (polling).
When the module is configured as a client, the module writes the input data to the
application.
Further topics
"C
onfiguring the TCP/IP socket interfaces", page 20
PROJECT PLANNING 4
8024581/2020-11-10 | SICK O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1
15
Subject to change without notice
5 Mounting
5.1 Safety
WARNING
E
lectrical voltage
There is a risk of injury from electrocution while connecting the devices.
b
Disconnect the power for the entire plant/machine.
WARNING
Unintended start of the plant/machine
The plant/machine could inadvertently start while you are connecting the devices.
b
Disconnect the power for the entire plant/machine.
5.2 Mounting procedure
For information on the mounting process, please see the operating instructions:
“F
lexi Compact” (SICK part number 8024573)
5.3 Module exchange
Approach
1.
Disconnect the module and the connected components from all voltage sources.
2. Dismantle the defective module.
3. Mount the new module.
5 MOUN
TING
16
O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1 8024581/2020-11-10 | SICK
Subject to change without notice
6 Electrical installation
6.1 Safety
WARNING
E
lectrical voltage
There is a risk of injury from electrocution while connecting the devices.
b
Disconnect the power for the entire plant/machine.
WARNING
Unintended start of the plant/machine
The plant/machine could inadvertently start while you are connecting the devices.
b
Disconnect the power for the entire plant/machine.
6.2 Device connection
Prerequisites
N
etwork cable requirement:
Type: 100Base-TX
Cables with RJ45 connections
Twisted pair Ethernet cable, maximum length 100 m in accordance with
EN 50173
Use of wire pairs 1/2 and 3/6
Shielded cables
Cat 5 STP or higher
Pin assignment
1
2
Figure 5: Connections
1
RJ45 female Ethernet connector
2
RJ45 female Ethernet connector
ELECTRICAL INSTALLATION 6
8024581/2020-11-10 | SICK O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1
17
Subject to change without notice
7 Configuration
7.1 Offline, online and security configuration
Overview
All c
onfiguration parameters are assigned to a configuration group. The configuration
groups differ, for example, when transmitting and saving the configuration.
The following configuration groups are available
Offline configuration
Online configuration
Security configuration
Offline configuration
All of
fline configuration parameters are written to the safety controller using the Transfer
to device function. The offline configuration includes, for example, all parameters of the
hardware configuration.
These parameters can only be configured in the configuration software.
To configure the parameters, no connection to the safety controller must exist. Only
establish a connection to the safety controller when you want to transfer the configura‐
tion.
The application is stopped while the configuration is transferred to the safety controller.
The offline configuration is stored in the SmartPlug. A (defective) module can be
replaced with a compatible module without having to reconfigure the device. The offline
configuration must be compatible with the physical safety controller.
Within the offlline configuration, a distinction is made between the following configura‐
tion data.
Configuration data:
Safety configuration
Configuration data that affect the safety function of a device, e.g., configuration of
s
afety capable inputs, safety outputs, logic, …
S
tandard configuration
Configuration data that affect the non-safety function of a device, e.g., configura‐
t
ion of test outputs, configuration of non-safe modules.
N
on-functional configuration
Configuration data that have no effect on the functioning of the device, e.g. tag
name
s, comments in the logic, project information of the user
Online configuration
Each of the online configuration parameters have their own transfer option and can
be individually written to the safety controller. The online configuration includes, for
example, the parameters relating to the network settings.
These parameters can be configured in the configuration software or via a module with
a display.
To configure the parameters using the configuration software, a connection to the
safety controller must exist.
The application does not need to be stopped while the configuration is transferred to
the safety controller.
The online configuration is saved in and read back from the SmartPlug using the mod‐
ule position and the module type. If the module position is maintained, a (defective)
module can be replaced with a compatible module without having to reconfigure the
7 C
ONFIGURATION
18
O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1 8024581/2020-11-10 | SICK
Subject to change without notice
device. If the module position is changed, the saved parameters will not work. If, for
e
xample, the module position of a gateway is changed, the connection parameters
need to be reconfigured before a connection to the safety controller can be established.
The old module positions are corrected when writing an offline configuration.
If online configuration parameters are configured without a SmartPlug inserted, these
settings will only apply temporarily until the safety controller is restarted or a SmartPlug
is inserted.
Security configuration
T
he security configuration includes the following parameters:
Passwords for user groups
These parameters can only be configured in the configuration software.
The application does not need to be stopped while the configuration is transferred to
the safety controller.
The security configuration is saved in the SmartPlug. A (defective) module can be
replaced with a compatible module without having to reconfigure the device.
Further topics
"Smar
tPlug"
"Display menu", page 25
7.2 Configuring the network interfaces
7.2.1 Configuring the higher-level controller
Approach
1.
Load the device description file into the configuration software of the higher-level
controller. Follow the instructions in the online help or in the user manual of the
configuration tool to do so.
2. Search the hardware catalog to find the desired device, e.g., use the search
function and enter “SICK”.
3. Add the device to the project and connect to the controller.
4. Select submodules of the cyclical process data. Only one input submodule and
one output submodule can be active at any one time.
5. Specify where they are to be addressed in memory.
6. Configure properties such as the update time for the cyclical I/O data exchange of
the gateway.
7. Assign a PROFINET name to the gateway.
Complementary information
You can find the device description file and device symbol on the gateway product page
at www.sick.com.
The selected submodules of the higher-level controller must match the selected sub‐
modules in the configuration software.
CONFIGURATION 7
8024581/2020-11-10 | SICK O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1
19
Subject to change without notice
7.2.2 Addressing
7.2.2.1 Configuring the connection data
Overview
T
he IP address is normally assigned by the PROFINET controller (e.g. higher-level control
system). The gateway also allows you to configure the safety controller via TCP/IP. In
this case, it may be necessary to assign an IP address to the gateway before setting up
the PROFINET network.
Approach
1. In the main navigation pane, click Configuration.
2. In the navigation tree of the required module, select the Addressing menu item.
3. Enter the device name in the PROFINET name field.
4. Enter the IP address, the Subnet mask, and an IP address for a Standard gateway.
Complementary information
The MAC address is printed on the type label of the device.
7.2.2.2 Reading and transmitting values
Overview
If t
he values in the project and the values in the device differ, you can read the values
from the device and apply them to the project or transfer the values from the project to
the device.
Approach
1. In the main navigation pane, click Configuration.
2. In the navigation tree of the required module, select the Addressing menu item.
3. Perform the required action:
°
Click on Read from device. The values are read from the device and adopted in
the project.
°
Click on Transmit to device. The values are read from the device and adopted in
the project.
7.2.3 Deactivating alarms
Approach
1.
In the main navigation pane, click Configuration.
2. In the navigation pane under GPNT, select the PROFINET Alarms menu item.
3. Select the Alarms are inactive option.
The alarms will no longer be transmitted to the higher-level control system.
7.2.4 Configuring the TCP/IP socket interfaces
Overview
T
he module supports four TCP/IP socket interfaces. Multiple applications can commu‐
nicate with the safety controller at the same time. For each TCP/IP socket, six connec‐
tions are possible, i.e. 24 connections in total.
The TCP/IP socket interfaces operate in parallel to the PROFINET interface.
7 C
ONFIGURATION
20
O P E R A T I N G I N S T R U C T I O N S | Flexi Gateway GPNT1 8024581/2020-11-10 | SICK
Subject to change without notice
  • Page 1 1
  • Page 2 2
  • Page 3 3
  • Page 4 4
  • Page 5 5
  • Page 6 6
  • Page 7 7
  • Page 8 8
  • Page 9 9
  • Page 10 10
  • Page 11 11
  • Page 12 12
  • Page 13 13
  • Page 14 14
  • Page 15 15
  • Page 16 16
  • Page 17 17
  • Page 18 18
  • Page 19 19
  • Page 20 20
  • Page 21 21
  • Page 22 22
  • Page 23 23
  • Page 24 24
  • Page 25 25
  • Page 26 26
  • Page 27 27
  • Page 28 28
  • Page 29 29
  • Page 30 30
  • Page 31 31
  • Page 32 32
  • Page 33 33
  • Page 34 34
  • Page 35 35
  • Page 36 36
  • Page 37 37
  • Page 38 38
  • Page 39 39
  • Page 40 40
  • Page 41 41
  • Page 42 42
  • Page 43 43
  • Page 44 44
  • Page 45 45
  • Page 46 46
  • Page 47 47
  • Page 48 48
  • Page 49 49
  • Page 50 50
  • Page 51 51
  • Page 52 52
  • Page 53 53
  • Page 54 54
  • Page 55 55
  • Page 56 56